Enable Communication Protocols
Liebert
®
IntelliSlot
®
Unity
™
Card
16
Figure 10 BACnet MSTP settings
3.1.3 Enable SNMP
SNMPv1/v2c and SNMPv3 are enabled by default. The protocols may be configured or their default
values may be accepted. Authentication Traps are not enabled by default. The default Heartbeat Trap
interval is 24 hours; this can be disabled or the interval may be changed.
1. Select the Unity Tab > Protocols > SNMP.
2. Click on
Edit
and enter a User name and password if required.
3. To enable Authentication Traps, put a check mark (
✔
) in the box.
4. To change the Heartbeat Trap Interval, choose a time from the drop-down list or choose Disabled
to prevent any heartbeat traps from being sent.
The interval times offered are 5 minutes, 30 minutes, or 1, 4, 8, 12 or 24 hours.
5. Choose whether to disable the traps or to set the interval to one of the periods on the menu.
6. Click
Save
to confirm the changes or click on
Cancel
to discard them.
7. Restart the card to activate the changes.
a. Select the Unity Tab > Support.
b. Enable the commands.
c. Click on
Restart
.