background image

Liebert

®

 IntelliSlot

®

 Unity Card

User Manual–Web, SNMP, Modbus, BACnet, YDN23

Activity

Link

485

IS-UNITY-DP

Summary of Contents for Liebert IntelliSlot Unity-DP

Page 1: ...Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 Activity Link 485 IS UNITY DP ...

Page 2: ......

Page 3: ...b Page Sections 21 4 2 Help Text 23 4 3 Managed Equipment Tab Menus 24 4 4 Unity Tab Menus 25 5 0 EDIT THE LIEBERT INTELLISLOT UNITY CARD CONFIGURATION 26 5 1 Web Page Unity Tab Folders 27 5 1 1 Unity Tab Active Events Folder 27 5 2 Unity Tab Downloads Folder 27 5 3 Unity Tab Configuration Folder 27 5 3 1 Configuration Folder System 28 5 3 2 Configuration Folder User Settings 28 5 3 3 Configuratio...

Page 4: ...e protocols enable commands 11 Figure 6 Modbus TCP Trusted IP List 12 Figure 7 Modbus RS 485 13 Figure 8 BACnet protocol settings 14 Figure 9 BACnet IP settings 15 Figure 10 BACnet MSTP settings 16 Figure 11 SNMP settings 17 Figure 12 SNMPv3 user settings 18 Figure 13 SNMPv1 trap settings 19 Figure 14 SNMPv1 v2c access settings 20 Figure 15 Web page sections UPS example 22 Figure 16 Web page secti...

Page 5: ...PS s Contact Liebert Services at 1 800 LIEBERT 1 800 543 2378 WARNING Risk of electric shock Can cause equipment damage injury or death Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations and manufacturers specifications Opening or removing the covers to any equipment may expose personnel to lethal voltages w...

Page 6: ...erson Protocol Remote Service Delivery Protocol and HTTP Web by default The Liebert IntelliSlot Unity DP supports selecting two third party protocols the Liebert IntelliSlot Unity LIFE card supports the default protocols only Emerson Protocol Remote Service Delivery Protocol and HTTP Web Available protocols are BACnet IP BACnet over Internet Protocol BACnet MSTP BACnet Master Slave Token Passing M...

Page 7: ...rk will be able to view status information Modbus TCP and Modbus RTU Support The Liebert IntelliSlot Unity card supports Modbus TCP and Modbus RTU for the full range of information available from the managed device The Modbus protocol mapping document SL 28170 is available at Liebert s Web site www liebert com BACnet IP and BACnet MSTP Support The Liebert IntelliSlot Unity card supports BACnet IP ...

Page 8: ...r Liebert IntelliSlot Unity platform communication interfaces Liebert Nform Support Utilizing the Emerson Protocol or SNMP and Web technologies built into each Liebert IntelliSlot Unity card Liebert Nform will centrally manage alarm notifications to provide an easy interface to access critical equipment information A downloadable version is available online at nform liebert com Liebert MultiLink S...

Page 9: ...ot Mode as described in Static IP on page 6 Connect an RJ 45 cable to the card and it will receive an IP address from the DHCP server Contact the DHCP administrator to obtain the IP address using the Liebert IntelliSlot Unity card s MAC address The MAC address is printed on the card s faceplate If the DHCP administrator is not available or there is no way of determining the IP address assigned by ...

Page 10: ...adapter being used to attach to the card does not show an Autoconfiguration IPv4 Address open a new Command Prompt and type ipconfig renew and press Enter This forces the computer to acquire an Autoconfiguration IPv4 Address 4 When the computer has an Autoconfiguration IPv4 Address open a browser window on the computer and type 169 254 24 7 the card s default Autoconfiguration IPv4 Address in the ...

Page 11: ...tep 3 with the negative terminal and the black wire 6 Plug the cable into the 485 RJ 45 port on the Liebert IntelliSlot Unity card 2 2 Change User Names and Passwords Immediately Emerson recommends changing the administrative user name and password immediately to safeguard protected configuration and control areas of the Liebert IntelliSlot Unity card The user name and password are set at the fact...

Page 12: ...Unity Tab Configuration Network Settings 2 Enable the protocol either IPv4 or IPv6 that will be used to communicate with the Liebert IntelliSlot Unity card and with the Liebert equipment a Click on either IPv4 Settings or IPv6 Settings b Click the Edit button c When prompted with a login display enter the user name and password the defaults are Liebert and Liebert d Put a check mark in the enabled...

Page 13: ... the first and second cards are both Liebert IntelliSlot Unity cards steps must be taken to avoid duplicate Emerson Protocol MSTP node ID s By default the two cards would use the same node ID and one or both cards would report a duplicate node error and fail to communicate with the system The default node ID for a Liebert IntelliSlot Unity card is 0 so the second card should use 1 or 2 preferably ...

Page 14: ...er the administrator user name and password 3 Put a check mark in the desired protocols Only two may be enabled only one of the two can use the 485 port 4 Click Save to confirm the changes or click on Cancel to discard them 5 Configure the protocols selected For details refer to 5 0 Edit the Liebert IntelliSlot Unity Card Configuration 6 Restart the card refer to 5 11 Configuration Unity Tab Suppo...

Page 15: ...igure Modbus RTU For additional details see 5 7 Protocols Folder Modbus Configure Modbus TCP 1 Select the Unity Tab Protocols Modbus TCP 2 Click on Edit and enter a User name and password if required 3 Set the Limit Network Access Type by choosing from the drop down list Open Same Subnet Trusted IP List Refer to 5 7 Protocols Folder Modbus for additional details 4 Enter the port to be used by the ...

Page 16: ...lue from 1 to 255 that is unique among devices connected through the RS 485 interface The default baud rate is 9600 19200 and 38400 also available Contact your system administrator if you are uncertain about the settings 4 Click Save to confirm the changes or click on Cancel to discard them 5 Restart the card to confirm the changes a Select Unity Tab Support b Enable the commands c Click on Restar...

Page 17: ...r Read Write This determines a user s ability to change settings in the Liebert IntelliSlot Unity card 4 Choose the BACnet interface either BACnet IP or BACnet MSTP 5 Set the Device Object Instance Number 6 Set the Device Object Name 7 Set the APDU Timeout 8 Set the APDU Retries 9 Click Save to confirm the changes or click on Cancel to discard them 10 Configure the BACnet interface chosen refer to...

Page 18: ...e Liebert IntelliSlot Unity card is on a different subnet a possibility when the monitored units are part of a Liebert SiteScan network or other third party monitoring service a Choose whether to enable Register as Foreign Device b Enter the IP address of the BBMD BACnet Broadcast Management Device c Enter a time in seconds for Foreign Device Time to Live 5 Click Save to confirm the changes or cli...

Page 19: ...net MSTP 2 Click on Edit and enter a user name and password if required 3 Set the BACnet MSTP Node ID The ID default is 1 4 Set the BACnet MSTP Data Rate 5 Set the BACnet MSTP Max Master Address 6 Set the BACnet MSTP Max Info Frames The default is 8 7 Click Save to confirm the changes or click on Cancel to discard them 8 Restart the card to activate the changes a Select Unity Tab Support b Enable ...

Page 20: ...lick on Edit and enter a User name and password if required 3 To enable Authentication Traps put a check mark in the box 4 To change the Heartbeat Trap Interval choose a time from the drop down list or choose Disabled to prevent any heartbeat traps from being sent The interval times offered are 5 minutes 30 minutes or 1 4 8 12 or 24 hours 5 Choose whether to disable the traps or to set the interva...

Page 21: ...v3 users must have settings configured SNMPv1 trap settings are separate from the access settings for SNMPv1 v2c Configure SNMPv3 Settings The settings must be made for each user who will receive notifications 1 Select Unity Tab Protocols SNMP SNMPv3 Users Setting 20 SNMPv3 Users Setting 1 2 Click on Edit and enter a User name and password if required 3 Enter the information and set the permission...

Page 22: ...ame and password if required 3 Enter the information and set the permissions appropriate to the user Refer to Figure 13 for the information required 4 Click Save to confirm the changes or click on Cancel to discard them 5 Repeat Steps 1 through 4 for any additional users 6 Restart the card to confirm the changes a Select the Unity Tab Support b Enable the commands c Click on Restart Settings are r...

Page 23: ...Enable Communication Protocols 19 Liebert IntelliSlot Unity Card Figure 13 SNMPv1 trap settings Settings required for each address that will receive SNMP notifications ...

Page 24: ...and set the permissions appropriate to the user Refer to Figure 13 for the information required 4 Click Save to confirm the changes or click on Cancel to discard them 5 Restart the card to confirm the changes The card must be restarted before another user s settings may be changed a Select the Unity Tab Support b Enable the commands c Click on Restart Figure 14 SNMPv1 v2c access settings Selecting...

Page 25: ... Managed Equipment tab which will display the name of the monitored equipment and the Unity Tab The tab selected determines the Tab Menu shown Managed Equipment Tab Information pertaining to the equipment being monitored and controlled Refer to 4 3 Managed Equipment Tab Menus for details The tab label refers to the type of Liebert unit the card is installed in Figure 15 shows a Managed Equipment T...

Page 26: ...tification Status Tab Menu changes according to monitored equipment Unity Tab Managed Equipment Tab Card in a Liebert APM Information on Opening Screen depends on type of unit being monitored Identification Status Tab Menu changes according to monitored equipment Unity Tab Information on Opening Screen depends on type of unit being monitored Managed Equipment Tab Card in a Liebert CRV ...

Page 27: ...de the Status Events or Setting entry Figure 17 Help text on mouse over Table 3 Help text and icons Icon Description a check mark on a green button Event Normal an i on a blue button Event Information an x on a red button Event Alarm an exclamation point on a yellow shield Event Warning an exclamation point on a red button Event Critical an i in a word balloon Tool Tip i x i Hovering a mouse point...

Page 28: ...t IntelliSlot Unity card installed in a UPS differ from menus shown by a card installed in Thermal Management equipment Information on those menus will also differ depending on the equipment the card is installed in Figure 18 Managed Equipment Tab examples Liebert APS and Liebert CRV Equipment tab will display Status or Events for the applicable equipment only Equipment tab will display Status Eve...

Page 29: ...eeds to be reconfigured RS 485 Port Conflict Duplicate Emerson Protocol MSTP Node ID Duplicate BACnet MSTP Node ID Shows the overall condition of the system and whether a restart is needed to activate configuration changes restart is performed only from the Support Folder page 42 Support Agent time and Date Agent Model Agent App Firmware Version Agent App Firmware Label Agent Boot Firmware Version...

Page 30: ...the card s IP address 2 Click on the Unity Tab 3 Select the menu in the Tab Menu area that contains the configuration setting to be changed 4 Click the Edit button near the top of the Web page see Figure 19 5 Enter the administrator name and password for the Liebert IntelliSlot Unity card in the dialog box that opens the default settings are Liebert and Liebert 6 Click OK 7 Change the settings 8 C...

Page 31: ...Unity card 5 2 Unity Tab Downloads Folder The Unity Tab s Downloads folder contains no configurable settings The folder displays links to download logs of third party protocols that are enabled on the Liebert IntelliSlot Unity card The logs help in configuring and troubleshooting communication between the Network Management or Building Management Systems being used to monitor the managed equipment...

Page 32: ...urce to be used for time synchronization NTP Time Server Network Time Server NTP URL or IP address NTP Time Sync Rate The rate at which time will be synchronized with the Network Time Protocol server if NTP is the external time source Time Zone Time zone where the device is located Enable Auto Sync to Managed Device Enable automatic writing time to the managed device Managed Device Auto Sync Rate ...

Page 33: ...and IPv6 settings determine which Internet Protocol will be used for communication over the network connected to the Ethernet port IPv4 and IPv6 networks will run in parallel dual stack network but the protocols are different See your network administrator to determine which protocol should be enabled and to determine the correct settings Figure 22 IPv4 IPv6 settings IPv4 Settings IPv4 Protocol En...

Page 34: ...Example gxtwebdemo liebert com resolved to 126 4 203 234 Type of Query Type of DNS query Hostname IP Address Query Value Value for the domain name server DNS to resolve Example gxtwebdemo liebert com 5 3 4 Configuration Folder Web Server Settings The Web Server Settings permits making some security settings such as HTTP or HTTPS and password enabling Web Server Settings Web Server Protocol Select ...

Page 35: ...ed Device MSTP Ethernet and Internal 5 4 Configuration Folder Messaging Settings The Messaging Settings subfolder permits enabling e mail and text messaging about events The subfolder also contains a test to determine whether the notifications are sent Settings for the two notification methods permit specifying who gets the notifications the format and other details Email May be enabled to send e ...

Page 36: ...ill be included in outgoing messages Include Event Description in Message If checked SNMP event description will be included in outgoing messages Include Name in Message If checked the agent card Name will be included in outgoing messages Include Contact in Message If checked the agent card Contact will be included in outgoing messages Include Location in Message If checked the agent card Location...

Page 37: ...ecked the agent card Name will be included in outgoing messages Include Contact in Message If checked the agent card Contact will be included in outgoing messages Include Location in Message If checked the agent card Location will be included in outgoing messages Include Description in Message If checked the agent card Description will be included in outgoing messages Include Web Link in Message I...

Page 38: ...t IP BACnet MSTP Modbus Modbus TCP Modbus RTU SNMP SNMPv3 User Settings 20 SNMPv1 Trap Settings 20 SNMPv1 v2c Access Settings 20 YDN23 Settings in each permit configuring the protocols available on the Liebert IntelliSlot Unity card 5 6 Protocols Folder BACnet Folder BACnet Settings Managed Device Write Access Enable or Disable the BACnet server to write to the managed device BACnet Interface BACn...

Page 39: ...Time to Live Time to remain in the BBMD Foreign Device table after registration 5 6 2 Protocols Folder BACnet MSTP Folder BACnet MSTP Settings Node ID The BACnet server s MS TP node ID MAC Data Rate The BACnet MSTP communication rate bits per second Max Master Address The maximum node ID MAC in use on the MS TP network Max Info Frames Maximum number of information frames this node may send before ...

Page 40: ...ists only five addresses are permitted Modbus TCP Settings Limit Network Access Type IP Access List Open Same Subnet Trusted IP List Port The TCP port used by the Modbus Server to listen for and respond to Modbus protocol requests based on Limit Network Access Type setting Maximum Client Connection Count 5 7 2 Modbus RTU Modbus RTU Settings Node ID Modbus Server ID for the interface obtain from ne...

Page 41: ...d 24 hours RFC 1628 MIB Enable or Disable support for retrieval of data from the RFC 1628 MIB objects Required for proper operation of Liebert MultiLink and applies only to managed UPS equipment RFC 1628 MIB Traps Enable or Disable support for sending RFC 1628 traps Required for proper operation of Liebert MultiLink and applies only to managed UPS equipment Liebert Global Products LGP MIB Enable o...

Page 42: ...uble quote and question mark SNMPv3 Access Type Read Only Read Write or Traps only SNMPv3 Authentication Cryptographic algorithm used for authentication None MD5 or SHA 1 SNMPv3 Authentication Secret Pass phrase or password used for SNMPv3 Get request This string can be composed of printable characters with the exception of colon tab double quote and question mark Note The entry must be 8 or more ...

Page 43: ... beside the desired information see Figure 23 The choices permit showing the same information in this screen that is displayed by clicking on a SNMPv3 User Settings folder or a SNMPv3 User Settings link Figure 23 Edit the SNMPv3 table Click on this link to change the information shown in the table Checking all choices will display the information below on the SNMPv3 User Settings 20 page The infor...

Page 44: ... be changed by clicking on the link above the table SNMPv1 Trap Settings SNMP Trap Target Addresses Configure network hosts that will receive alert notifications i e SNMP Traps The host can be identified as either an IP address or the host s network name SNMP Trap Port Port used by the target host for receiving notifications default is 162 SNMP Trap Community String String identifying a secret kno...

Page 45: ...ders for the access hosts Also data shown in the table may be changed by clicking on the link above the table SNMPv1 v2c Access Settings SNMP Access IP Address Configure network hosts interested in device information access The host can be identified as either an IP address or the host s network name SNMP Access Type SNMPv1 v2C access type Read Only or Read Write SNMP Access Community String SNMP ...

Page 46: ...Device Write Access Enable or Disable the YDN23 server to write to the managed device Device Address YDN23 device address Baud Rate The communications rate in bps 5 10 Configuration Unity Tab Status Folder The Status folder contains no configurable items It displays the System Status of the Liebert IntelliSlot Unity card and a list of events that affect the card s status A green check mark indicat...

Page 47: ...d s firmware label Agent Boot Firmware Version The card s Boot firmware version Agent Boot Firmware Label The card s boot firmware label Agent Serial Number The card s serial number Agent Manufacture Date The card s manufacture date Agent Hardware Version The card s hardware version GDD Version The card s GDD version current when the card s firmware was installed the GDD is a proprietary reference...

Page 48: ...resently used IPv4 Primary DNS IPv4 Secondary DNS Presently used IPv4 Secondary DNS Last DHCP BootP Last known IPv4 address assigned by DHCP Last DHCP Lease Lease time of last known DHCP address IPv6 Global Address Shows if DHCPv6 or Static address is presently being used IPv6 StateLess Address AutoConfiguration IPv6 SLAAC is assigned automatically from Router Advertisement if A flag is set combin...

Page 49: ...rmware running on the card Current Firmware Label The label of the firmware running on the card Current Firmware Date The build date of the firmware running on the card Alternate Firmware Version The version of the firmware in the alternate area Alternate Firmware Label The label of the firmware in the alternate area Alternate Firmware Date The build date of the firmware in the alternate area Comm...

Page 50: ...net RJ 45 connector on the front see Figure 24 The card and computer will automatically negotiate communications which will take about one minute for details on autoconfiguration see 2 1 2 Connect an Ethernet Cable When communication is established open a Web browser and enter the address 169 254 24 7 the card s default Autoconfiguration IPv4 Address The card s Web page will appear Figure 24 Ether...

Page 51: ... Unity Card Figure 25 Firmware update screen Support Folder Firmware Update Web button becomes active when enabled and administrator s user name and password are entered Enable Button User name and password must be entered to update firmware ...

Page 52: ...Enter the user name and password in the security dialog box that appears use the administrator user name and password from the user settings 5 Click on the Run Alternate button and a confirmation dialog box will appear 6 Click the OK button on the confirmation dialog box NOTE Reverting to an alternate firmware version will not be possible if the currently operating firmware is the initial version ...

Page 53: ...fe_callInterval_hours Call Trials Number The number of attempts to retry a call after it fails before rescheduling the call Settings Description Primary Mains Restored SMS Send SMS when Primary Mains are restored Primary Mains Restored SMS Value Value sent via SMS when Primary Mains are restored Primary Mains Failure SMS Send SMS when Primary Mains fail Primary Mains Failure SMS Value Value sent v...

Page 54: ...r Scheduled Call Delay Time The delay time before the next call to the LIFE Watch Station server Heartbeat Status Device status as determined by heartbeat traps Date and Time UTC of Last Call The date and time in UTC of the LIFE Watch Station that was retrieved when the last successful call was made YY MM DD HH MM SS Commands Description Make Manual Call Sends all currently collected events Reset ...

Page 55: ......

Page 56: ...ebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upstech emerson com 800 222 5877 Outside North America 00800 1155 4499 Three Phase UPS Power Systems 800 543 2378 Outside North America 614 841 6598 Environmental Systems 800 543 2778 Outside the United States 614 888 0246 Locations United States 1050 Dearborn Drive P O Box 2918...