Table 4-11 Cable ratings (400 V)
Table 4-12 Cable ratings (575 V)
Table 4-13 Cable ratings (690 V)
PVC insulated cable should be used.
Cable sizes are from IEC60364-5-52:2001 table A.52.C with correction factor for 40°C ambient of 0.87 (from table A52.14) for cable installation
method as specified.
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input
Output
Input
Output
Nominal Maximum
Installation Nominal Maximum Installation Nominal Maximum
Nominal Maximum
03400025
1.5
4
B2
1.5
4
B2
18
10
18
10
03400031
16
16
03400045
14
14
03400062
2.5
2.5
03400078
03400100
12
12
04400150
4
6
B2
4
6
B2
10
8
10
8
04400172
6
6
8
8
05400270
6
6
B2
6
6
B2
8
8
8
8
05400300
06400350
10
25
B2
10
25
B2
6
3
6
3
06400420
16
16
4
4
06400470
25
25
3
3
07400660
35
70
B2
35
70
B2
1
1/0
1
1/0
07400770
50
50
2
2
07401000
70
70
1/0
1/0
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input
Output
Input
Output
Nominal Maximum
Installation Nominal Maximum Installation Nominal Maximum
Nominal Maximum
05500030
0.75
1.5
B2
0.75
1.5
B2
16
16
16
16
05500040
1
1
14
14
05500069
1.5
1.5
14
14
06500100
2.5
25
B2
2.5
25
B2
14
3
14
3
06500150
4
4
10
10
06500190
6
6
10
10
06500230
10
10
8
8
06500290
6
6
06500350
16
6
6
07500440
16
25
B2
16
25
B2
4
3
4
3
07500550
25
25
3
3
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input
Output
Input
Output
Nominal Maximum
Installation
method
Nominal Maximum
Installation
method
Nominal Maximum
Nominal
Maximum
07600190
10
25
B2
10
25
B2
8
3
8
3
07600240
6
6
07600290
6
6
07600380
16
16
4
4
07600440
16
16
4
4
07600540
25
25
3
3
NOTE