114
E300 Installation and Commissioning Guide
Issue Number: 1
A10
(
Control Input Mode
H11
)
This parameter allows the user to configure the input control mode. The following configurations are available:
Analog Run Prmit (0): Analog speed reference with run permit
Run permit and
Direction Input 1
CCW (
G39
) = On (1) to start the profile. The analog reference is bi-directional i.e. the direction of travel is taken from
the sign of the analog reference where –ve references are
Counter Clockwise
(CCW) and +ve references are
Clockwise
(CW) direction.
Direction
Input 2
CW (
G40
) has no effect in this mode.
•
Sequencing may be started when the enable is received. It is assumed that the enable is made via an auxiliary contact on the output motor
contactors. Motor contactor control output
is not used when the enable starts the sequencing.
•
Sequencing may be started when a run permit input is given. Motor contactor control is set to On (1) when the run permit (direction) signal is
given. It is assumed that the enable is made via an auxiliary contact on the output motor contactors.
•
When an analog speed reference mode is selected
Analog Input 1 Destination
(
F41
) is forced to
Analog Speed Reference
(
G49
).
T5 T6 Analog
Input 1
(
F35
) must be used as the speed reference input.
Analog 2 Dir (1): Analog speed reference with dual direction inputs.
The analog reference is read from the analog speed reference input. If
Direction Input 1 CCW
(
G39
) = Off (0) and
Direction Input 2 CW
(
G40
) = On
(1), clockwise direction is selected, and if
Direction Input 1
CCW (
G39
) = On (1) and
Direction Input 2
CW (
G40
) = Off (0) counter clockwise direction
is selected. If
Direction Input 1
CCW (
G39
) and
Direction Input 2
CW (
G40
) = On (1) or Off (0) no direction is selected.
•
Sequencing may be started when the enable is received. It is assumed that the enable is made via an auxiliary contact on the output motor
contactors. Motor contactor control is not used when the enable starts the sequencing.
•
Sequencing may be started when a direction input is given
Direction Input 1
CCW (
G39
) or
Direction Input 2
CW (
G40
) = On (1)).
Motor contactor
control output
(
B29
) is set to On (1) when the direction signal is given. It is assumed that the enable is made via an auxiliary contact on the output
motor contactors.
Priority 1 Dir (2): Single direction input and priority speed selection
Priority speed selection where for example V2 higher priority than V3.
Direction Input 1
CCW (
G39
) = Off (0) clockwise direction is selected, and
Direction Input 1
CCW (
G39
) = On (1) counter clockwise direction is selected.
Binary 1 Dir (3): Single direction input and binary speed selection
Binary speed selection and
Direction Input 1
CCW (
G39
) = Off (0) clockwise direction is selected, and
Direction Input 1
CCW (
G39
) = On (1) counter
clockwise direction is selected.
Priority 2 Dir (4): Dual direction input with priority speed selection
Priority speed selection where for example V2 has higher priority than V3,
Direction Input 1
CCW (
G39
) = Off (0) and
Direction Input 2
CW (
G40
) =
On (1) clockwise direction is selected, and if
Direction Input 1
CCW (
G39
) = On (1) and
Direction Input 2
CW (
G40
) = Off (0) counter clockwise
direction is selected. If
Direction Input 1
CCW (
G39
) and
Direction Input 2
CW (
G40
) = On (1) or Off (0) then no direction is selected.
Binary 2 Dir (5): Dual direction input and binary speed selection
Direction Input 1
CCW (
G39
) = Off (0) and
Direction Input 2
CW (
G40
) = On (1) clockwise direction is selected, and if
Direction Input 1
CCW (
G39
) =
On (1) and
Direction Input 2
CW (
G40
) = Off (0) counter clockwise direction is selected. If
Direction Input 1
CCW (
G39
) and
Direction Input 2
CW
(
G40
) = On (1) or Off (0) then no direction is selected. Changing the direction during travel will cause the elevator to abort the present motion and
come to a stop.
Control Word (6): Dual direction selection, and priority 10 bit selection using control word.
When Control input mode = 6 the control word is enabled. The control word replicates and extends the behaviour of the reference select bits,
Reference select bit 0 to Reference select bit 6, and the direction bit inputs,
Direction Input 1
CCW (
G39
) and direction Input 2 (CW). A watchdog is
provided to verify that the Elevator controller using the control word is still updating the speed and direction inputs. The user must write 1 to the
watchdog bit every < 500 ms to prevent the watchdog from stopping the Elevator and causing a
Trip 77
(
Ctrl Watchdog
)
.
When the system is powered on when
Control Input Mode
(
H11
) = Control Word (6) or when
Control Input Mode
(
H11
) is set to Control Word (6) for
the first time after power up, a 10 s delay is implemented before calling a
Trip 77
(
Ctrl Watchdog
). This delay allows the lift controller time to start up
after power on and begin writing to the watchdog bit in the control word. The delay reverts back to 1 s after this initial period.
A10 {H11}
Control Input Mode
RW
Txt
US
OL
Ú
Analog Run Prmit (0),
Analog 2 Dir (1),
Priority 1 Dir (2),
Binary 1 Dir (3),
Priority 2 Dir (4),
Binary 2 Dir (5),
Control Word (6)
Ö
Priority 1 Dir (2)
RFC-A
RFC-S