E300 Installation and Commissioning Guide
119
Issue Number: 1
A18
(
Motor Rated Current
B02
)
Enter the motor name plate value for the motor rated current.
A19
(
Motor Rated Voltage
B03
)
Enter the motor name plate value for the motor rated voltage
A20
(
Motor Number Of Poles
B05
)
The numeric value in number of motor poles should be set to the number of motor pole pairs (i.e. number of motor poles / 2). The text string
associated with number of motor poles indicates the number of motor poles (i.e. the parameter value x 2).
Open-loop
This parameter is used during the calculation of the motor speed and in then applying the correct slip compensation. When Automatic (0)
is selected, the number of motor poles is automatically calculated from the motor rated frequency and motor rated speed. The number of poles = 120
x rated frequency / rpm rounded to the nearest even number.
RFC-A
This parameter must be set correctly for the vector control algorithms to operate as expected. When Automatic (0) is selected the number of
motor poles is automatically calculated from the motor rated frequency and motor rated speed rpm. The number of poles = 120 x rated frequency /
rpm rounded to the nearest even number.
RFC-S
This parameter must be set correctly for the vector control algorithms to operate as expected. If Automatic (0) is selected in RFC-S mode the
number of poles are set = 3 pole pairs (6) and no calculation is carried out.
A21
(
Motor Rated Frequency
B06
)
Enter the motor name plate value for the motor rated frequency
A18 {B02}
Motor Rated Current
RW
Num
RA
US
OL
Ú
±VM_RATED_CURRENT
A
Ö
Maximum Heavy Duty
Rating
(
J05
)
RFC-A
RFC-S
A19 {B03}
Motor Rated Voltage
RW
Num
RA
US
OL
Ú
±VM_AC_VOLTAGE_
SET V
Ö
200 V drive: 230 V
50 Hz default 400 V drive: 400 V
60 Hz default 400 V drive: 460 V
575 V drive: 575 V
690 V drive: 690 V
RFC-A
RFC-S
A20 {B05}
Number Of Motor Poles
RW
Txt
US
OL
Ú
Automatic (0) to
480 Poles (240)
Ö
Automatic (0)
RFC-A
RFC-S
Ö
6 Poles (3)
A21 {B06}
Motor Rated Frequency
RW
Num
US
OL
Ú
0.0 to 550.0 Hz
Ö
50 Hz default: 50.0 Hz
60 Hz default: 60.0 Hz
RFC-A
RFC-S