87
EATON
www.eaton.com
Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Register
Name
Attribute
Description
326
Temperature of pole C (Temp C)
UINT16 RO
Units:
O
C
Pole C Temperature in degrees C.
327
Maximum Temperature
UINT16 RO
Units:
O
C
Maximum Temperature of all SCR Poles in degrees C.
328
Max temperature of pole A
(Resettable)
UINT16 RW
Units:
O
C
Pole A Maximum Temperature in degrees C.
329
Max temperature of pole B
(Resettable)
UINT16 RW
Units:
O
C
Pole B Maximum Temperature in degrees C.
330
Max temperature of pole C
(Resettable)
UINT16 RW
Units:
O
C
Pole C Maximum Temperature in degrees C.
331
Line Voltage Phase Order
UINT8 RO
AC Line Phase Rotation 0
ABC, 1
ACB
332
Pre-start sub-fault code
UINT8 RO
Pre-Start checks results
333
RTC Second
UINT8 RW
Real Time Clock Seconds
334
RTC minute
UINT8 RW
Real Time Clock Minutes
335
RTC hour
SINT16 RW
Real Time Clock Hours
336
AutoZeroOffset_CurrPhA
SINT16 RW
337
AutoZeroOffset_CurrPhB
SINT16 RW
338
AutoZeroOffset_CurrPhC
SINT16 RW
339
currentRaw_phaseA_maxPeak
SINT16 RW
340
currentRaw_phaseB_maxPeak
SINT16 RW
341
currentRaw_phaseC_maxPeak
SINT16 RW
342
currentRaw_phaseA_minPeak
SINT16 RW
343
currentRaw_phaseB_minPeak
SINT16 RW
344
currentRaw_phaseC_minPeak
SINT16 RW
400
KW
SINT16 RO
Units: kW, IP
Calculated Real Power in kW
401
kVA
SINT16 RO
Units: kVA
Calculated Apparent Power in kVA
402
kVAR
SINT16 RO
Units: kVAR
Calculated Reactive Power in kVAR
403
Power Apparent Power Factor
SINT16 RO
Calculated Apparent Power Factor
404
Motor Max Starting Current - Per
Last Start
UINT16 RO
Units: Arms
Maximum Starting Current recorded during last start
405
Analytical Motor Terminal Voltage
(Anal. Mtr. Volt)
UINT16 RO
Units: Volts
406
Firing Angle (Alpha Angle)
UINT16 RW
Units: Degrees
407
Residual Ground Current RMS
UINT16 RO
Units: Arms
408
Current Unbalance
UINT16 RO
Units: %
409
Voltage Unbalance
UINT16 RW
Units: %
415
Number of Motor Starts During the
Last hour
UINT16 RO
Number of Motor Starts during the last hour
416
Last Measured Starting Time. Time to
get up to speed
UINT16 RO
Units: Sec
Last measured Start Time; Time to get up to speed
417
Time since the Last Start
UINT32 RO
Units: Sec
Time since the last start
419
Motor Run Time Total
UINT32 RW
Units: Hr: Min: Sec
Motor Run Time total
421
Motor Run Time Latest Run - How
long the motor was running last time.
UINT32 RO
Units: Hr: Min: Sec
Motor Run Time during the latest run
423
Number of Motor Starts User
(Resettable)
UINT32 RW
Number of Motor Starts since the last reset (resettable)
425
Fault Queue - Event List
UINT16 RO
Number of Events (1 to 10) in order of occurrence