119
EATON
www.eaton.com
Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Topic
Parameter
Units
Description
IP Conflict Detection Status
Address Conflict Detection State. This is read only.
0 = No conflict detected.
1 = Conflict detected - defending.
2 = Conflict detected - retreated.
IP conflict Detection Conflicted
MAC
Address Conflict Detection conflicted device MAC address. The source MAC address
from the header of the received Ethernet packet which was sent by a device reporting
a conflict. All Ethernet devices have a unique MAC address, so by reporting the MAC
address of the device containing the duplicate IP address allows the issue to be
resolved in a timely manner.
Ethernet Port 1 Enable
This parameter is used to disable the Ethernet port.
True = Enable Port
False = Disable Port
Ethernet Port 1 Autonegotiate
Enable
Selects Auto-Negotiation of link speed and duplex.
False = Disabled
True = Enabled
Ethernet Port 1 Autonegotiate
State
Active state of the Auto-Negotiation behavior. This parameter indicates the status of
the auto negotiate on the Ethernet network. This is read only.
Ethernet Port 1 Full Duplex
Enable
Selects the duplex mode. Only used when Auto-Negotiate is disabled.
True = Full Duplex
False = Half Duplex
Ethernet Port 1 Full Duplex
Enabled
Actual duplex mode. This is a read only parameter, indicting the actual duplex mode
on the Ethernet network.
True = Full Duplex
False = Half Duplex
Ethernet Port 1 Speed Select
Select the Ethernet link speed. Only used when Auto-Negotiate is disabled.
10 = 10 Mbps
100 = 100 Mbps
Ethernet Port 1 Speed Actual
Actual Ethernet link speed. This parameter is used to verify the data rate being used
on the Ethernet network. It is read only.
Ethernet Port 2 Enable
This parameter is used to disable the Ethernet port.
True = Enable Port
False = Disable Port
Ethernet Port 2 Autonegotiate
Enable
Selects Auto-Negotiation of link speed and duplex.
False = Disabled
True = Enabled
Ethernet Port 2 Autonegotiate
State
Active state of the Auto-Negotiation behavior. This parameter indicates the status of
the auto negotiate on the Ethernet network. This is read only.
Ethernet Port 2 Full Duplex
Enable
Selects the duplex mode. Only used when Auto-Negotiate is disabled.
True = Full Duplex
False = Half Duplex
Ethernet Port 2 Full Duplex
Enabled
Actual duplex mode. This is a read only parameter, indicting the actual duplex mode
on the Ethernet network.
True = Full Duplex
False = Half Duplex
Ethernet Port 2 Speed Select
Select the Ethernet link speed. Only used when Auto-Negotiate is disabled.
10 = 10 Mbps
100 = 100 Mbps
Ethernet Port 2 Speed Actual
Actual Ethernet link speed. This parameter is used to verify the data rate being used
on the Ethernet network. It is read only.
Base Control
Module
Base Control Module Assigned
Name
Base Control Module User Assigned Name. The default is "Power Xpert C445," but
optionally may be changed.
Base Control Module Product
Code
Base Control Module Product Code (numerical format)