PROGRAMMING
SINUS K
MANUAL
80/
226
P69 MDO 11/16
P
P69
R
0÷200%
D
0%
Level = *.*** %
F
Determines the value for the activation of Open collector digital output for
the following settings: “Reference level”, “Frequency level”, “Forward
Running”, “Reverse Running”, “Current level”, “FB Max”, “FB Min”, “Fout
O.K.”, “PID O.K.”.
P70 MDO. fr. 12/16
P
P70
R
0÷200%
D
0%
hyst. = *.***%Hz
F
When Open Collector digital output is set as “Reference Level”, “Frequency
level”, “Forward Running”, “Reverse Running”, “Current level”, “Fout O.K.”,
“PID O.K.”, “FB Max”, “FB Min”, this parameter determines the digital output
hysteresis range.
If the hysteresis is other than 0, the value set with P69 when the quantity set
with P60 increases determines the output commutation; when the output
decreases, commutation occurs when the value set in P69–P70 is reached
(Example: Set P60 = “Frequency level”, P69 = 50%, P70 = 10%; the digital
output activates when 50% of the preset maximum output frequency is
reached and deactivates when 40% is reached).
If P70 = 0, commutation occurs when the value set in P69 is reached.
Open Collector MDO digital output set as “PID Max Out” and “PID Min Out”
determines the value for the digital output deactivation. The digital output
activates when PID regulator output (expressed as a percentage) reaches the
value set for P90 “PID Max Out” and P89 “PID Min Out” respectively, and
deactivates when the value set for P90 – P70 and P89 + P70 is reached (see
Figure 6.6 and Figure 6.7)
P71 RL1 13/16
P
P71
Level = *.*** %
R
0 ÷200%
D
0 %
F
Determines the value for the activation of relay digital output RL1 for the
following settings: “Reference level”, “Frequency level”, “Forward Running”,
“Reverse Running”, “Current level”, “FB Max”, “FB Min”, “Fout O.K.”, “PID
O.K.”.