PROGRAMMING
SINUS K
MANUAL
92/
226
First page
Press PROG (Esc) to return to the V/f Pattern submenu access page. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
parameters.
PARAMETERS OF THE V/F PATTERN SUBMENU
C05 V/f patt. 2/17
P
C05
R
1A÷Column “Inom”, Table 6.4
D
Column “Imot”, Table 6.4
I mot. = *** A
F
Rated current of the connected motor
C06 V/f patt. 3/17
P
C06
R
3.5÷800 Hz for S05÷S30
R
3.5÷120 Hz for S40÷S70
D
50 Hz
fmot 1= *** Hz
F
Motor rated frequency relating to the first v/f pattern. Determines switching from the
inverter operation at constant V/f to the inverter operation at constant V.
C07 V/f patt. 4/17
P
C07
R
3.5÷800 Hz for S05÷S30
R
3.5÷120 Hz for S40÷S70
D
50 Hz
Fomax1 = *** Hz
F
Maximum output current relating to the first voltage/frequency pattern. Inverter output
frequency at maximum reference value.
C08 V/f patt. 5/17
P
C08
R
0.1÷5Hz
D
0.1 Hz
Fomin1 = *** Hz
F
Minimum output frequency relating to the first V/f pattern. Minimum frequency
generated at the inverter output (can be altered only after contacting Elettronica
Santerno).
C09 V/f patt. 6/17
P
C09
R
5÷500V (class 2T, 4T)
R
5÷690V (class 5T, 6T)
D
230V for class 2T
D
400V for class 4T
D
575 for class 5T
D
690 for class 6T
Vmot1 = *** V
F
Motor rated frequency relating to the first V/f pattern. Determines output voltage at
motor rated frequency.
C10 V/f patt. 7/17
P
C10
R
–100%÷+100%
D
0 %
Boost1 = *** %
F
Torque compensation at low rpm relating to the first V/f pattern. Determines output
voltage increment at low output frequency with respect to a constant V/f ratio.
PROG SAVE
V/f Pattern 1/17
Ent Prv Nxt