SINUS-K
PROGRAMMING
MANUAL
157/
226
7.3.5.
A
UTORESET
S
UBMENU
The Autoreset submenu enables the automatic reset of the equipment when alarms trip. Autoreset attempts may be set
in a given time interval.
Access page
Press PROG (Ent) to access the first page of the Autoreset submenu. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
submenus.
First page
Press PROG (Esc) to return to the Autoreset submenu access page. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
parameters.
PARAMETERS OF THE AUTORESET SUBMENU
C46 Attempts 2/4
P
C46
R
0÷10
D
0
Number = *
F
Determines the number of automatic reset operations performed before locking the
function. Autoreset count starts from 0 after a time period longer than the one set in
C52 is over.
NOTE
If C46 = 0 is set, the autoreset function is locked.
C47 Clear fail 3/4
P
C47
R
1÷999s
D
300s
count time ***s
F
Determines the time interval clearing the autoreset count if no alarm trips.
C48 PWR Reset 4/4
P
C48
R
NO, YES
D
NO
[NO] YES
F
Set to YES to automatically reset an alarm by switching off and on the inverter.
PROG SAVE
Menu Autoreset
Ent Prv Nxt
PROG SAVE
Autoreset 1/4
Ent Prv Nxt
V
T
C