PROGRAMMING
SINUS K
MANUAL
96/
226
C23 Op. method 4/12
P
C23
R
Mltf1, Up, Var%1, Stop, Fire Mode
D
Mltf1
Determines functionality of multifunction input 1 (terminal 9):
Mltf1: multifrequency input 1.
Up: output frequency increment key (P24 allows the new value to be stored at power
off).
MDI1 = ***
F
Var%1: input percent variation of frequency reference 1.
Stop: Stop button (to be used in conjunction with the Start contact – terminal 7 –
which will act as a button).
Fire Mode: any protection feature of the inverter is ignored, so that no alarm trips
when the inverter is running.
CAUTION
Due to the activation of the Fire Mode function, the inverter guarantee should be no
longer valid if the conditions for the activation of a protection function occur.
If an asterisk (*) appears next to INVERTER OK on the display, the inverter guarantee is
no longer valid.
C24 Op. meth.1 5/12
P
C24
R
Mltf2, Down, Var%2, Loc/Rem, Fire Mode
D
Mltf2
Determines functionality of multifunction input 2 (terminal 10):
Mltf2: multifunction input 2.
F
Down: output frequency decrement key (P24 allows the new value to be stored at
power off).
Var%2: input percent variation of frequency reference 2.
MDI2= ***
Loc/Rem: KeyPad mode forced.
Fire mode: any protection feature of the inverter is ignored, so that no alarm trips
when the inverter is running.
CAUTION
Due to the activation of the Fire Mode function, the inverter guarantee should be no
longer valid if the conditions for the activation of a protection function occur.
If an asterisk (*) appears next to INVERTER OK on the display, the inverter guarantee is
no longer valid.
C25 Op. method 6/12
P
C25
R
Mltf3, CW/CCW, DCB, Var%3, REV, A/M, Lock, Loc/Rem
D
Mltf3
Determines functionality of multifunction input 3 (terminal 11):
Mltf3: multifunction input 3.
CW/CCW: reversal of the direction of rotation.
DCB: direct current braking command.
Var%3: variation per cent input of frequency reference 3.
REV: reverse direction command.
A/M: PID regulator deactivation command.
Lock: keypad lock command.
MDI3= ***
F
Loc/Rem: KeyPad mode forced.