SINUS-K
PROGRAMMING
MANUAL
87/
226
PARAMETERS OF THE REF VAR% SUBMENU
P75 Ref Var% 2/8
P
P75
R
–100%
÷
+100%
D
0%
Var% 1 = ***
F
Determines the output frequency variation when multifunction digital input 1
(terminal 9) is active and set as percent reference variation (parameter C23, OP
METHOD submenu).
P76 Ref Var% 3/8
P
P76
R
–100%
÷
+100%
D
0%
Var% 2 = ***
F
Determines the output frequency variation when multifunction digital input 2
(terminal 10) is active and set as percent reference variation (parameter C24, OP
METHOD submenu).
P77 Ref Var% 4/8
P
P77
R
–100%
÷
+100%
D
0%
Var% 3 = ***
F
Determines the output frequency variation when multifunction digital inputs 1 and 2
(terminals 9 and 10) are active and set as percent reference variation (parameters
C23, C24, OP METHOD submenu).
P78 Ref Var% 5/8
P
P78
Var% 4 = ***
R
–100%
÷
+100%
D
0%
F
Determines the output frequency variation when multifunction digital input 3
(terminal 11) is active and set as reference percent variation (parameter C25, OP
METHOD submenu).
P79 Ref Var% 6/8
P
P79
R
–100%
÷
+100%
D
0%
Var% 5 = ***
F
Determines the output frequency variation when multifunction digital inputs 1 and 3
(terminals 9 and 11) are active and set as percent reference variation (parameter
C23, C25, OP METHOD submenu).
P80 Ref Var% 7/8
P
P80
R
–100%
÷
+100%
D
0%
Var% 6 = ***
F
Determines the output frequency variation when multifunction digital inputs 2 and 3
(terminals 10 and 11) are active and set as percent reference variation (parameter
C24, C25, OP METHOD submenu).
P81 Ref Var% 8/8
P
P81
R
–100%
÷
+100%
D
0%
Var% 7 = ***
F
Determines the output frequency variation when multifunction digital inputs 1, 2, and
3 (terminals 9, 10, 11) are active and set as percent reference variation (parameter
C23, C24, C25, OP METHOD submenu).
IFD