SINUS-K
PROGRAMMING
MANUAL
159/
226
C50 FanForce 3/17
P
C50
R
NO, YES
D
NO
[NO] YES
F
Fan startup forced.
NO: Fan starts when heatsink temperature > 60°C;
YES: Fan continuous operation.
CAUTION
This parameter is effective for inverter models where fans are controlled by the inverter
control board (“P” or “N” appear in the relevant field – see Section 5.2 Inverter Ratings).
This parameter has no effect for inverter models where fans are controlled directly from
the power circuit (“B ” or “S” appear in the relevant field).
C51 FluxDis. 4/17
P
C51
R
0÷1350 s
D
0 s
time = *** s
F
Time period after which the inverter automatically deactivates if terminal 6 closes,
terminal 7 opens and reference drops to 0. Set this parameter to 0 to disable this
function.
C52 Mains l.m 5/17
P
C52
R
NO, YES
D
NO
[NO] YES
F
Stores any alarm relating to mains failure (A30 and A31) causing the equipment
power off. When power supply is restored, send a RESET command to reset the
alarms tripped.
C53 ENABLE 6/17
P
C53
[NO] YES
R
NO, YES
D
YES
F
Operating conditions of ENABLE command (terminal 6) at power on or when a
RESET command is sent:
NO: ENABLE command deactivated at power on or after RESET; if terminals 6 and
7 are active and a speed reference is sent, at power on or after an alarm RESET, the
motor does not start until terminal 6 is opened and closed again.
YES: ENABLE activated at power on; if terminals 6 and 7 are active and a speed
reference is sent, the motor starts at power on or after a few seconds a RESET
command is sent.
DANGER
Setting parameter C53 to YES may start the motor as soon as the inverter is switched on.
C54 First 7/17
P
C54
R
Keypad, Status
D
Status
F
page = ***
Determines which pages are displayed at power on:
Status: Access page to the main menus
Keypad: Page relating to the command sent via keypad.
V
T
C