C26 Encoder 14/16
P
C26
R
100÷10000
D
1024
pulse = ***
F
Number of the encoder pulses per revolution.
C27 Delay 15/16
P
C27
R
0÷1500 rpm
D
0 rpm
Run spd = *** rpm
F
If this speed value is not increased, no start command is acknowledged after a stop
command until the deceleration ramp is over, time set in C51 is over and the inverter
is disabled.
Set C27=0 to disable this function.
If C51 is set to 0, the run command is locked because the sequence cannot be
terminated. Always set C51 other than 0 when using this function.
C28 PIDinv.16/16
P
C28
R
NO, YES
D
NO
[NO] YES
F
If C28=YES is programmed, it adds a unit negative gain to the PID loop, i.e. it
inverts the PID error (see relevant chapter).