PROGRAMMING
SINUS K
MANUAL
196/
226
10.4.
SPECIAL PARAMETERS (SPxx) (Read Only)
Description
Addr.
(dec)
Addr.
(hex)
Min Max
K
Unit of
meas.
SP01 Terminals
reference
769
301
0
1023
1
Note 09
SP04 Configuration
bit
772
304
Note 10
SP05 Configuration
bit
773
305
Note 11
SP09 Inverter
condition
777
309
0
24
Note 12
Note 09 Result of 10–bit A/D conversion of analog inputs in terminal board RIFV1, RIFV2, RIFI downstream of
processing with parameters P16, P17, P18, P19, P20.
Note 10 SP04 Configuration bit: address 772 (304 hex)
Bit
P39 MF.FUNCTION
0
0 Absolute
1 Sum
P23 U/D – KPD MIN
1
0 0
1 +/–
C62 FIRST PAGE
2
0 Status
1 Keypad
C57 BRAKE UNIT
3
0 Provided
1 Not provided
C21 START OPER. M.
4
Along with bit 773.11.
C22 REF OPERATION M.
5
Along with bit 773.12.
P18 VREF J14 POSITION
6
0 Unipolar
1 Bipolar
C86 DCB HOLD
7
0 Disabled
1 Enabled
C40 ACCELERATION LIM.
8
Along with 773.6
C42 RUNNING LIM.
9
0 Disabled
1 Enabled
C31 PID INVERSION
10 0 Disabled
1 Enabled
C50 AUTORESET
10 0 Disabled
1 Enabled
C60 MAINS LOSS MEM.
11 0 Not stored
1 Stored
C55 SPEED SEARCHING
12 Along with bit 773.2
C80 DCB AT STOP
13 0 Disabled
1 Enabled
C81 DCB AT START
14 0 Disabled
1 Enabled
C61 ENABLE OPERATION
15 0 Activated after opening
1 Immediately activated
Note 11 SP05 Configuration bit: address 773 (305 hex)
Bit
P24 UP/DOWN MEM.
0
0 Not stored
1 Stored
C04 SILENT MODULATION
1
0 Disabled
1 Enabled
C55 SPEED SEARCHING
2
Along with bit 772.2
C53 PWR RESET
3
0 Disabled
1 Enabled
P25 UP/DOWN RESET
4
0 Disabled
1 Enabled
C35 POWER DOWN
5
0 Disabled
1 Enabled
C40 ACCELERATION LIM.
6
Along with bit 772.8
C44 DECELERATION LIM.
7
0 Disabled
1 Enabled
C34 MAINS L.
8
0 Disabled
1 Enabled
C92 WATCHDOG
9
0 Disabled
1 Enabled
C46 F. W. RED.
10 0 Disabled
1 Enabled
C21 START REM ENABLE
11 Along with bit 772.4
C22 FREF REM ENABLE
12 Along with bit 772.5
C54 HIGH V
13 0 380-480V (4T)
Not used (2T / 5T / 6T)
1 481-500V (4T)
C69 BRK BOOST
14 0 Disabled
1 Enabled
C58 FANFORCE
15 0 Fan always ON
1 Starting fan if T>60°C