PROGRAMMING
SINUS K
MANUAL
146/
226
7.2.10.
S
PEED
L
OOP
S
UBMENU
The Speed Loop submenu includes the parameters relating to speed regulator adjustment.
Access page
Press PROG (Ent) to access the first page of the PID Regulator submenu. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
submenus.
First page
Press PROG (Esc) to return to the Speed Loop submenu access page. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
parameters.
PARAMETERS OF THE SPEED LOOP SUBMENU
P100 Spd Prop2/4
P
P100
R
0÷32
D
5.0
gain = ***
F
Defines the value of speed regulator proportional term.
P101 Spd lnt 3/4
P
P101
R
0÷10 s – NONE
D
0.5 s
time = ***s
F
Defines the value of speed regulator integral time. Set “NONE” to disable integral
term.
102 ZeroSpd 4/4
P
P102
R
0÷500%
D
100%
const = ***%
F
Multiplicative constant of the proportional term, which is applied with a speed
reference = 0 and the START contact (terminal 7) open.
PROG SAVE
Menu Speed Loop
Ent Prv Nxt
PROG SAVE
Speed Loop 1/4
Ent Prv Nxt