6-10 Communications
CMD
(hex) Name
Function
28 Inc Spt
Advances one edge of a pulse, both edges, or all pulses in a
channel, by one scale factor increment.
Cmd:
! ADR
28 XX YY ZZZZ TTTT MM CSM <CR>
Reply:
A <CR>
where “XX” is the program number minus one, and “YY” is the
channel number minus one.
“ZZZZ” and “TTTT” are the
current “on” and “off” points of the
pulse, respectively.
“MM” specifies the scope of the change: “00” is the “off” edge;
“01” is the “on” edge; “02” is both edges of the pulse; and “03” is
all edges of all pulses in the channel. All values are in hex.
29 Dec Spt
Retards one edge of a pulse, both edges, or all pulses in a
channel, by one scale factor increment.
Cmd:
! ADR
29 XX YY ZZZZ TTTT MM CSM <CR>
Reply:
A <CR>
where “XX” is the program number minus one, and “YY” is the
channel number minus one.
“ZZZZ” and “TTTT” are the
current “on” and “off” points of the
pulse, respectively.
“MM” specifies the scope of the change: “00” is the “off” edge;
“01” is the “on” edge; “02” is both edges of the pulse; and “03” is
all edges of all pulses in the channel. All values are in hex.
30 Def Disp
Default display on start-up.
Put:
! ADR
30 P XX CSM <CR>
Reply:
A <CR>
Get:
! ADR
30 G CSM <CR>
Reply:
A XX CSM <CR>
where “XX” is the display mode: “00” is Speed, “01” is Position,
and “02” is Auto.
31 Tog RPM
Toggle RPM speed.
Put:
! ADR
31 P XXXX CSM <CR>
Reply:
A <CR>
Get:
! ADR
31 G CSM <CR>
Reply:
A XXXX CSM <CR>
where “XXXX” is the toggle RPM speed in hex.
57 Rate Setup
Multiplier and units for RPM display.
Put:
! ADR
57 P XX YY CSM <CR>
Reply:
A <CR>
Get:
! ADR
57 G CSM <CR>
Reply:
A XX YY CSM <CR>
“XX” is the multiplier: “01” = 1X; “02” = 2X; “03” = 3X; “04” = .5X.
“YY” = units: “00” = RPM; “01” = BPM; “02” = CPM
Serial Commands (cont’d)
Display
Commands
Setpoint
Commands
(cont’d)