5.1.2.6 Analog 4-20 mA Outputs Configuration.
The instrument supports two 4-20 mA or 0-20 mA analog outputs with 500 ohms maximum load. Each output
is to one of the parameters handled by the instrument.
The output is updated every 10 cycles of the network frequency (i.e. every 200mSec with 50 Hz mains) with
a maximum delay of 50 mSec from the actual measurement.
(A)Output identification, A.o.1 = Analog output 1.
(1) Parameter applying. The possible choices are:
--
Disabled
U
Voltage
f Frequency
I Current
P Active
Power
Q Reactive
Power
S Apparent
Power
λ
(PF)
Power Factor
THD
U
Total Harmonic Distortion (Voltage)
THD
I
Total Harmonic Distortion (Current)
(2) Parameter definition: The possible choices are:
Average star value (applicable to voltage, current and THD only).
Average system value (applicable to voltage and THD only).
Neutral value (applicable to current only)
Three phase value (applicable to active, reactive and apparent power only)
L1
Phase 1 Value.
L2
Phase 2 Value.
L3
Phase 3 Value.