Pag. 115 di 152
The service configuration parameters are stored in the following input variables:
Events Service – Input variables
Name
ID
Type
Range
Default
Unit
Description
Max data-file size
FF00h
DWORD (ID 02h)
Unsigned integer
-
All space
available
on disk
bytes
Maximum admitted size
for each data file
Max data-file number
0400h
WORD (ID 01h)
Unsigned integer
1÷255
4
-
Maximum number of files
allowed on disk
Voltage Dip/Sag
&
Undervoltage
Threshold
0401h
DWORD (ID 02h)
Unsigned integer
5÷100 %
of F.S.
80
V
Triggering threshold for Voltage
Dip/sag and Overvoltage start
Voltage Dip/Sag
&
Undervoltage
Restore Threshold
0402h
DWORD (ID 02h)
Unsigned integer
5÷100 %
of F.S.
100
V
Restore threshold for Voltage Dip/sag
and Overvoltage end
Voltage Dip/Sag
Max Duration
0403h
WORD (ID 01h)
Unsigned integer
1-11700
72
cycles
Maximum duration of Voltage Dip/Sag
Voltage Swell
&
Overvoltage
Threshold
0404h
DWORD (ID 02h)
Unsigned integer
240
V
Triggering threshold for Voltage Swell
and overvoltage start
Voltage Swell
&
Overvoltage
Restore Threshold
0405h
DWORD (ID 02h)
Unsigned integer
235
V
Restore threshold for Voltage Swell
and overvoltage end
Voltage Swell
Max Duration
0406h
WORD (ID 01h)
Unsigned integer
1-11700
72
cycles
Maximum duration of Voltage Swell
Current Peak
&
Overcurrent
Threshold
0407h
DWORD (ID 02h)
Unsigned integer
500
A/100
Triggering threshold for current peaks
and Overcurrent start.
Current Peak
&
Overcurrent
Restore Threshold
0408h
DWORD (ID 02h)
Unsigned integer
450
A/100
Restore threshold for current peaks
and Overcurrent end.
Current Peak
Max Duration
0409h
WORD (ID 01h)
Unsigned integer
11700
cycles
Maximum duration of Current peak
Events detection
enable
040Ah
WORD (ID 01h)
Unsigned integer
03h
bitmapped
1
≡
Voltage Dip/Sag enabled
1
≡
Voltage Swell enabled
1
≡
Current Peaks enabled
3
Equivalent to three minutes with 65Hz mains frequency