91
9.4.5 Coils (back compatibility)
Coils area compatible with the previous instruments:
Coils, back compatibility
Address Description
Note:
0
Clear AVG (1,3)
Reset all the power values in floating average
1
Clear AVG (1,3)
as 0001
2
Clear MD (1,3)
Reset all the power peak values
3
Clear MD (1,3)
as 0003
4
Clear energy counters (1)
Reset all the energy counters
5
Warm boot (1)
Reinitialize the instrument (does not reset the counters)
6
AVG/MD synchronization (1,3)
Synchronize the integration period
7
Clear MD (1,3)
as 0003
8 Not
allocated
9
Out 1 (3)
Controls output nr. 1 (if the alarm use is inhibited)
10
Out 2 (3)
Controls output nr. 2 (if the alarm use is inhibited)
11 Not
allocated
12
Digital outs watchdog enable (3)
Protection Timer on inputs in minutes
13 Not
allocated
14 Not
allocated
15 Not
allocated
16 Not
allocated
17
Swap words & bytes (2, 4)
Format Control of the memory stored data
18 Not
allocated
9.4.6 X3M coils
Proprietary X3M coils area.
X3M Coils
Address Description
Note:
64
Swap bytes (5)
Data format control in memory
65 Swap
words
(5)
Data format control in memory
66
Reset (warm boot) (1,2)
Reinitialize the device (does not reset the counters)
67
Clear energy counters (1,2)
Reset all the energy counters
68
Power integration synchronization (1,2)
Synchronize the integration time.
69
Clear AVG powers (1,2)
Reset all the power value in moving average
70
Clear MD powers (1,2)
Reset all the power peak values
71
NOT USED (1)
(1) Reading the coil the result is always 1.
(2) The command is triggered on the leading edge, that is when the coil is set to 1 (TRUE). It is not necessary to set the
coil to 0 after setting it to 1.
(4) Negative logic, to be compatible with Kilo:
Coil = 1 Swap Bytes = Swap Words = FALSE (Motorola like, as Modbus standard)
Coil = 0 Swap Bytes = Swap Words = TRUE (Intel like).
The measurement resets “Swap Bytes” flag status (negative).
(5) If set to 1 (TRUE), it inverts the bytes order (or word order) respect to the modbus standard (Motorola like).