Pag. 110 di 152
10.3.1 Service configuration
The “load profiles logging” service makes use of the following output variables:
Load Profile Logging service – Output Variables
Name
ID
Type
Description
System clock
UTC
FF80h
Unix Timestamp (ID 06h)
Unix Tim offset (ID 07h)
Unix Tim DST flag (ID 08h)
Date (ID 09h)
Hour (ID 0Ah)
Date/Hour (ID 0Bh)
System clock, UTC
System clock
WALL TIME
FF81h
Unix Timestamp (ID 06h)
Unix Tim offset (ID 07h)
Unix Tim DST flag (ID 08h)
Date (ID 09h)
Hour (ID 0Ah)
Date/Hour (ID 0Bh)
System clock, WALL TIME
Timezone name
FF82h
BYTE ARRAY (ID 05h)
ASCIIZ string
Timezone name in use
Firmware version
FF83h
BYTE ARRAY (ID 04h)
Unsigned integer, Unsigned integer
Firmware version
(Major version, Minor version)
Slave ID
FF84h
WORD
(Unsigned integer)
Instrument slave ID (Modbus)
Serial number
FF85h
DOUBLEWORD
(Unsigned integer)
Instrument serial number
Event ID
0180h
WORD
(Unsigned integer)
Numeric code of the event initiating the
sampling:
0 Power
down
1 Power
up
2 Service
startup
3 Scheduled
sample
4
Clock changed from
5
Clock changed to
6 Configuration
changed
7 Counters
reset
8 Runtime
error
The service configuration parameters are stored in the following input variables:
Load Profile Logging Service – Input Variables
Name
ID
Type
Range Default
Units
Description
Max data-file size
FF00h
DWORD (ID 02h)
Unsigned integer
-
The entire
available
disk
space
Bytes
Maximum size allowed for a data file
Max data-file number
0100h
WORD (ID 01h)
Unsigned integer
1÷255 60
-
Maximum number of files on disk
allowed
Sampling interval
0101h
WORD (ID 01h)
Unsigned integer
1÷60 15
Minutes
Sampling
interval