Pag. 122 di 152
Tariff Energy Counters service – Output variables
Name
ID
Type
Mandat.
4
Description
Er ind imp
0781h
QUADWORD (ID 03h)
YES
Import Reactive energy inductive
(high resolution)
Er cap imp
0782h
QUADWORD (ID 03h)
YES
Import Reactive energy capacitive
(high resolution)
Es imp
0783h
QUADWORD (ID 03h)
YES
Import Apparent energy
(high resolution)
Ea exp
0784h
QUADWORD (ID 03h)
YES
Export Active energy
(high resolution)
Er ind exp
0785h
QUADWORD (ID 03h)
YES
Export Reactive energy Inductive
(high resolution)
Er cap exp
0786h
QUADWORD (ID 03h)
YES
Export Reactive energy capacitive
(high resolution)
Es exp
0787h
QUADWORD (ID 03h)
YES
Export Apparent energy
(high resolution)
The service configuration parameters are stored in the following input variables:
Tariff Energy Counters Service – Input variables
Name
ID
Type
Range Default
Unit
Description
Max data-file size
FF00h
DWORD (ID 02h)
Unsigned integer
-
All space
available
on disk
bytes
Maximum admitted size
for each data file
Refresh Period
0700h
WORD (ID 01h)
Unsigned integer
0..65535
0
s
Refresh interval of the report file.
When not specified, it refreshes at
each time band changeover or
whenever the serial port requires a file
reading.
10.5.2 Reset
The content of a report file may be reset by simply removing the file.
This operation will generate a temporary service stall of few tenths of sec.; after checking and validation of
the configuration files a new report file will be generated.