51
Description of the operational reading functions implemented
READING OF ALL MEASUREMENTS
This is carried out by reading 65 words starting from the address 0810H or 0FE00H.
The meaning of the 130 bytes received is as follows:
- Type of instrument (TIPVIP = 0DH = 13 (Vip Energy))
- Instrument options (OPTION) (1st byte):
bit 7 = 0 (not used)
7
6
5
4
3
2
1
0
bit
-
0
1
1
-
-
-
1
==> Microvip3 Plus
bit 3 = 0 (not used)
bit 2 = 0 (not used)
bit 1 = 0 (not used)
bit 0 = 1 = serial option present
- Instrument options (OPTIO2) (2nd byte):
bit 7, 6, 5, 4, 3, 2, 1, 0 = 0 (not used)
- Instrument setup (CONFIG) (1st byte):
bit 7, 6, 2 = Integration time for averages:
7
6
5
4
3
2
1
0
bit
0
0
-
-
-
0
-
-
==> 10 minutes
0
1
-
-
-
0
-
-
==> 15 minutes
1
0
-
-
-
0
-
-
==> 20 minutes
1
1
-
-
-
0
-
-
==> 30 minutes
0
0
-
-
-
1
-
-
==> 60 minutes
0
1
-
-
-
1
-
-
==> 1 minute
1
0
-
-
-
1
-
-
==> 2 minutes
1
1
-
-
-
1
-
-
==> 5 minutes
bit 5, 4, 3 = 0 (not used)
Bit 1 = Selection of cogeneration / no cogeneration:
7
6
5
4
3
2
1
0
bit
-
-
-
-
-
-
0
-
==> no Cog. 4 (Standard1 / 2)
-
-
-
-
-
-
1
-
==> Cogeneration 4 active
Bit 0 = Selection of switching type:
7
6
5
4
3
2
1
0
bit
-
-
-
-
-
-
-
0
==> Star
-
-
-
-
-
-
-
1
==> Delta
- Instrument setup (CONFI2) (2nd byte):
bit 7 = selection of Standard 1/2:
7
6
5
4
3
2
1
0
bit
0
-
-
-
-
-
-
-
==> Standard 1 (Wh, varh) active
(with bit 1 of CONFIG = 0)
1
-
-
-
-
-
-
-
==> Standard 2 (Wh,VAh) active
(with bit 1 of CONFIG = 0)
Note :
bit 0 = keyboard Enabling/Disabling
7
6
5
4
3
2
1
0
bit
-
-
-
-
-
-
-
0
==> keyboard enabled
-
-
-
-
-
-
-
1
==> keyboard disabled
- Three-phase voltage (V)
- Three-phase current (I)
- Three-phase active power (W)
- Three-phase cosphi
- Phase L1 voltage (V)
- Phase L2 voltage (V)
- Phase L3 voltage (V)
- Phase L1 current (I)
- Phase L2 current (I)
- Phase L3 current (I)
- Phase L1 active power (W)
- Phase L2 active power (W)