21
Twelfth page (three-phase)
Data storage control page.
LOG on (off) : To activate (or de-activate) storage (using the SET key)
01 - 99 m (minutes) : Data recording rate (00 = 3 seconds)
00 - 100 (% mem) : % of memory used
ELCONTROL energy
MICROVIP3 Plus
3-PHASE ENERGY & HARMONIC ANALYZER
PAGE
PRG SELC SETC
PAPER
SEL
SET
m
MEM
5.2.2
ENERGY CONSUMPTION AND MAXIMUM DEMAND RESET
The SET button resets to zero the electrical energy consumption counts (KVArh, KVArh and kWh) and the average
three phase active, reactive and apparent power peak values.
This function of the SET button is enabled only while the seventh, eighth or ninth measurement page is displayed (i.e.
where these values appear).
If you press the SET button while the seventh or eight measurement page is displayed, the energy consumption meters
are reset to zero.
ELCONTROL energy
MICROVIP3 Plus
3-PHASE & HARMONIC ANALYZER
PAGE
PRG SELC SETC
PAPER
SEL
SET
kVArh
kWh
3 ø
If you press the SET button while the ninth measurement page is displayed, the peak values for average three-phase
active, reactive and apparent power are reset to zero.
The buffer used for calculating average power is also reset, so that this value remains invalid until the programmed
integration time has lapsed again.
A series of dashes is displayed.
ELCONTROL energy
MICROVIP3 Plus
3-PHASE ENERGY & HARMONIC
ANALYZER
PRG SELC SETC
PAPER
PAGE
SEL
SET
kVA
kW
kVAr
3 ø
Once you have reset values, press the PAGE key to return to measuring mode.