Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 42
Nome oggetto
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Heating/cooling status in
Thermostat
function = both
heating and
cooling;
Heating
– cooling
switchover = from
bus
1 Bit
C-W---
[1.100] heating/cooling
49
The communication object is received by the bus
. All’evento di commutazione i regolatori interni
degli stadi primario e ausiliario (se abilitato) commutano il modo di conduzione. Il modo di
conduzione attivo è segnalato dal
l’apposito simbolo sul display.
HVAC mode in
1 Byte
C-W---
[20.102] HVAC mode
50
The device receives the operating mode (HVAC mode) from a bus device with function of
supervisor. The operating mode received through this communication object can be later modified
by the user (in questo caso il termostato ambiente passa in controllo manuale).
HVAC forced mode in
1 Byte
C-W---
[20.102] HVAC mode
51
The communication object allows to receive the operating mode similarly to what happens with
the communication object HVAC mode; the difference is that the operating mode is received via
this object (with the exception of the AUTO command) can not be subsequently modified by the
user. The user can change the mode only after the forced HVAC mode has sent the AUTO
command.
HVAC mode out
1 Byte
CR-T--
[20.102] HVAC mode
83
Building protection HVAC
mode active
1 Bit
CR-T--
[1.11] DPT_State
101
HVAC manual mode
General
Device
operation as =
stand-
alone/chrono
1 Byte
C-WTU-
[20.102] HVAC mode
53
Chrono active status
General
Device
operation as =
stand-
alone/chrono
1 Bit
CR-T--
[1.011] state
54
Manual setpoint
2 Byte
C-W---
[9.001] temperature (°C)
55
Manual/forced setpoint active
status
1 Bit
CRWTU-
[1.011] state
56