Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 28
Parameter name
Conditions
Values
Filter type
Input X
= [AI] …
low
medium
high
This parameter is always available when the input is configured as analogic.
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Offset temperature
Input
X = [AI] …
0°C
[range -5°C … +5°C]
This parameter is always available when the input is configured as analogic.
Minimum change of value to send [K]
0,5
[range 0
…5]
This parameter is always available when the input is configured as analogic. When
set to 0 (zero), no value is sent at a change.
Cyclic sending interval
Input X different from disabled
no sending
[other values in the range
30 s … 120 min]
Threshold 1
Input X =
[AI] …
not active
/ below / above
This parameter is always available when the input is configured as analogic.
Vaue [°C]
Input
X = [AI] …
Threshold 1 = below or above
7
[range 0
… 50]
Threshold 2
Input
X = [AI] …
not active
/ below / above
This parameter is always available when the input is configured as analogic.
Value [°C]
Input
X = [AI] …
Threshold 2 = below or above
45
[range 0
… 50]
Hysteresis
Input
X = [AI] …
Threshold 1 = below or above
Threshold 2 = below or above
0,4 K
[other values in the range
0,2 K … 3 K]
Cyclic sending interval
Input
X = [AI] …
Threshold 1 = below or above
Threshold 2 = below or above
no sending
[other values in the range
30 s … 120 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Window contact sensor (from
input 1)
Input 1 = [DI] windows contact
sensor
1 Bit
CR-T--
[1.019] window/door
26
Window contact sensor (from
input 2)
Input 2 = [DI] windows contact
sensor
1 Bit
CR-T--
[1.019] window/door
27
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Anticondensation sensor (from
input 1)
Input 1 = [DI] anticondensation
sensor
1 Bit
CR-T--
[1.005] alarm
28
Anticondensation sensor (from
input 2)
Input 2 = [DI] anticondensation
sensor
1 Bit
CR-T--
[1.005] alarm
29
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Card holder contact sensor
(from input 1)
Input 1 = [DI] card holder contact
sensor
1 Bit
CR-T--
[1.018] occupancy
30
Card holder contact sensor
Input 2 = [DI] card holder contact
1 Bit
CR-T--
[1.018] occupancy
31