Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 48
Parameter name
Conditions
Values
Heating type
radiators
elettric
fan-coils
floor radiant panels
ceiling radiant panels
It defines the terminal used for the thermal exchange in the room. The choice affects
the parameters of the PWM control algorithm (Proportional band and Integral time) and
the control options.
Control type
2 point hysteresis
PWM (pulse width modulation)
continuous
Hysteresis
Control type = 2 point hysteresis
0,3 K
[other values in the range 0,2 K
… 3 K]
Cyclic sending interval
Control type = 2 point hysteresis,
continuous
no sending
[other values in the range
30 s … 120
min]
Min. change of value to send [%]
Control type = continuous
10
[range
0 … 100]
PWM cycle time
Control type = PWM
15 min
[range 5
… 240 min]
Proportional band [0,1 K]
Control type = continuous or PWM
*
[range 0
… 255]
The value is in tenths of Kelvin (K) degree.
*) The field contains a preset value that depend on the selected heating type (the value
can be modified):
radiators: 50 ( 5 K)
elettric: 40 (4 K)
fan-coils: 40 (4 K)
floor radiant panels: 50 (5 K)
ceiling radiant panels: 50 (5 K)
The value of the parameter Proportional band represents the max difference between
the setpoint temperature and the measured temperature that causes the max control
output.
Integral time [min]
Control type = continuous or PWM
*
[other values in the range 0
… 255 min]
*) The field contains a preset value that depend on the selected heating type (the value
can be modified):
radiators: 150 min
elettric: 100 min
fan-coils: 90 min
floor radiant panels: 240 min
ceiling radiant panels: 180 min