Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 79
Nr.
Name
Size
Flags
Datapoint Type
34
Room temperature (from bus)
2 Bytes
-
WC---
[9.1] DPT_Value_Temp
35
Humidity (2 bytes, from bus)
2 Bytes
-
WC---
[9.7] DPT_Value_Humidity
36
Humidity (1 byte, from bus)
1 Byte
-
WC---
[5.1] DPT_Scaling
37
Antistratification temperature (from bus)
2 Bytes
-
WC---
[9.1] DPT_Value_Temp
38
Outdoor temperature (from bus)
2 Bytes
-
WC---
[9.1] DPT_Value_Temp
39
Air quality (from bus)
2 Bytes
-
WC---
[9.8] DPT_Value_AirQuality
40
Coil temperature (from bus)
2 Bytes
-
WC---
[9.1] DPT_Value_Temp
41
Floor temperature (from bus)
2 Bytes
-
WC---
[9.1] DPT_Value_Temp
42
Flow temperature (from bus)
2 Bytes
-
WC---
[9.1] DPT_Value_Temp
43
Windows contact sensor 1 (from bus)
1 Bit
-
WC---
[1.19] DPT_Window_Door
44
Windows contact sensor 2 (from bus)
1 Bit
-
WC---
[1.19] DPT_Window_Door
45
Contact of card holder (from bus)
1 Bit
-
WC---
[1.18] DPT_Occupancy
46
Anticondensation (from bus)
1 Bit
-
WC---
[1.1] DPT_Switch
47
Weighted temperature
2 Bytes
R-CT--
[9.1] DPT_Value_Temp
48
Heating/cooling status out
1 Bit
R-CT--
[1.100] DPT_Heat_Cool
49
Heating/cooling status in
1 Bit
-
WC---
[1.100] DPT_Heat_Cool
50
HVAC mode in
1 Byte
-
WC---
[20.102] DPT_HVACMode
51
HVAC forced mode in
1 Byte
-
WC---
[20.102] DPT_HVACMode
52
Actual setpoint
2 Bytes
R-CT--
[9.1] DPT_Value_Temp
53
HVAC manual mode
1 Byte
-
WCTU- [20.102] DPT_HVACMode
54
Chrono active status
1 Bit
R-CT--
[1.11] DPT_State
55
Manual setpoint
2 Byte
-
WC---
[9.1] DPT_Value_Temp
56
Manual/forced setpoint active status
1 Bit
RWCTU- [1.11] DPT_State
57
Comfort setpoint (heating)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
58
Comfort setpoint (cooling)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
59
Standby setpoint (heating)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
60
Standby setpoint (cooling)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
61
Economy setpoint (heating)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
62
Economy setpoint (cooling)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
63
Building protection setpoint (heating)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
64
Building protection setpoint (cooling)
2 Bytes
RWCTU- [9.1] DPT_Value_Temp
65
Heating out command
1 Byte
R-CT--
[5.1] DPT_Scaling
65
Heating out command
1 Bit
R-CT--
[1.1] DPT_Switch
65
Heating and cooling out command
1 Bit
R-CT--
[1.1] DPT_Switch
65
Heating and cooling out command
1 Byte
R-CT--
[5.1] DPT_Scaling
66
Cooling out command
1 Byte
R-CT--
[5.1] DPT_Scaling
66
Cooling out command
1 Bit
R-CT--
[1.1] DPT_Switch
67
Auxiliary heating output command
1 Bit
R-CT--
[1.1] DPT_Switch
67
Auxiliary heating and cooling output command
1 Bit
R-CT--
[1.1] DPT_Switch
68
Auxiliary cooling output command
1 Bit
R-CT--
[1.1] DPT_Switch
69
Auxiliary heating disable
1 Bit
-
WC---
[1.3] DPT_Enable
70
Auxiliary cooling disable
1 Bit
-
WC---
[1.3] DPT_Enable