Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 29
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
(from input 2)
sensor
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Coil battery temperature
sensor (from input 1)
Input 1 = [AI] coil battery
temperature sensor
2 Byte
CR-T--
[9.001] temperature
(°C)
20
Coil battery temperature
sensor (from input 2)
Input 2 = [AI] coil battery
temperature sensor
2 Byte
CR-T--
[9.001] temperature
(°C)
23
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Temperature value sensor
(from input 1)
Input 1 = [AI] room temperature
sensor
2 Byte
CR-T--
[9.001] temperature
(°C)
20
Temperature value sensor
(from input 2)
Input 2 = [AI] room temperature
sensor
2 Byte
CR-T--
[9.001] temperature
(°C)
23
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Antistratification temperature
sensor (from input 1)
Input 1 = [AI] antistratification
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
20
Antistratification temperature
sensor (from input 2)
Input 2 = [AI] antistratification
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
23
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Floor surface temperature
sensor (from input 1)
Input 1 = [AI] floor surface
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
20
Floor surface temperature
sensor (from input 2)
Input 2 = [AI] floor surface
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
23
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Outdoor temperature sensor
(from input 1)
Input 1 = [AI] outdoor
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
20
Outdoor temperature sensor
(from input 2)
Input 2 = [AI] outdoor
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
23
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Temperature value sensor
(from input 1)
Input 1 = [AI] generic (NTC)
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
20
Temperature value sensor
(from input 2)
Input 2 = [AI] generic (NTC)
temperature sensor
2 Byte
CR-T--
[9.001] temperature °C
23
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Temperature threshold 1
sensor 1 - Switch
Input
1 = [AI] …
Threshold 1 = below or above,
Threshold 2 = below or above
1 Bit
CR-T--
[1.001] switch
21
Temperature threshold 2
sensor 1 - Switch
Input
1 = [AI] …
Threshold 1 = below or above,
Threshold 2 = below or above
1 Bit
CR-T--
[1.001] switch
22