Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 91
With regard to the configuration of the auxiliary stage, the same considerations expressed in the paragraph
concerning fan-coil control with ON / OFF or continuous speed control are valid. The offset of the secondary
stage, ΔT
Offset
, is particularly important and it corresponds to the parameter
Heating and / or cooling deviation
from setpoint
. By configuring
Deviation from the set point
(which can be differentiated between heating and
cooling if the communication objects for control are separated) = 0 K, the radiant panel and the fan-coil
function as two heating and / or cooling elements in parallel. If that parameter deviation from the setpoint is >
0 K, the fan-coil intervenes quickly in the early stages of the set up of the room, leaving the radiant panel the
task of bringing the room to the desired temperature.
VEL1
Tset
VEL2
VEL3
hysteresis
T room
Tset
T room
hysteresis
OFF
VEL1
VEL2
VEL3
OFF
Threshold Speed1
Threshold Speed2
Threshold Speed3
(T set
– T room)
Threshold Speed1
Threshold Speed2
Threshold Speed3
(T room
– T set)
TOffset
TOffset
T room
OFF
ON
Tset
Thysteresis
T room
OFF
ON
Tset
Thysteresis
TOffset
TOffset