Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 71
7.11
Energy saving
In order to realise energy-saving functions, window contacts (to detect the opening of windows or doors),
presence and movement sensors and card holders can be used.
The
Energy saving
folder includes the following secondary folders:
Window contacts
Presence sensors
Card holder
7.11.1
Window contacts
The
Window contacts
secondary folder appears if at least a sensor dedicated to this function is enabled i.e.
if at least one of the two conditions is verified:
1)
Inputs
Input 1 and/or Input 2 = [DI] windows contact sensor
2)
External sensors (from bus)
Windows contact sensor 1 or 2 (from bus) = enabled
For the function can be acquired up to four signals which are combined as a logic OR.
The
Window contacts
folder includes the following parameters:
Window contacts function
Wait time to building protection mode
7.11.1.1
Parameters and communication objects
Parameter name
Conditions
Values
Window contacts function
disabled
/ enabled
This parameter enables the window contact function.
Wait time to building protection mode
Window contacts function = enabled
00:01:00 hh:mm:ss
[campo 00:00:00 … 18:12:15]
Time interval before the automatic switching of the device to the Building protection
operating mode.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Window contact sensor (from
input 1)
Window contacts function =
enabled,
Input 1 = [DI] windows contact
sensor
1 Bit
CR-T-
[1.019]
window/door
26
Window contact sensor (from
input 2)
Window contacts function =
enabled,
Input 2 = [DI] windows contact
sensor
1 Bit
CR-T-
[1.019]
window/door
27
Windows contact sensor 1
(from bus)
Window contacts function =
enabled,
Window contact 1 = enabled
1 Bit
C-W--
[1.019]
window/door
43