OEM
CAREL code +030221791 - rel. 2.1 – 21/09/07
26
IMPORTANT WARNING:
after having replaced or checked the parts in the water circuit, check that the connections have
been carried out correctly and the corresponding seals have been used. Re-start the unit and perform a number of fill and
drain cycles (from 2 to 4), then, applying the safety procedure, check for any water leaks.
6.3
Component replacement
6.3.1
Fuses in the auxiliary circuits
Use fuses with the ratings indicated in Table 5.3.1.
models
KUES*
KUETR*
KUET1*
KUET2*
KUET3*
KUET4*
fuses F1-F 2
1 A, GL, 10.3 x 38 in fuse carrier on DIN rail (0605319AXX)
fuse F3 (pump)
1 A, fast-blow 10.3 x 38
in fuse carrier on DIN rail
(0605319AXX)
fuse 3 ***
2 A, T, 5x20
Table 5.3.1
***: only on the CP control board.
no description
Order code
1
Load-bearing frame
2
Supply/drain manifold
18C499A001
3
Drain circuit
13C499A034
4
Drain pump
KITPS00000
5
Fill solenoid valve
KITVC00040
6
Supply tank
7
Supply tank cover
UEKVASC000
8
Tank fill hose
9
Cylinder fill hose
10
Overflow pipe
UEKT0000XL
11
Corrugated drain pipe
13C479A001
Table
5.2.1