Refrigerant Piping Installation
Ecosaire
®
July 2009 25
Data subject to change without notice.
Air-Cooled Direct Expansion and DualCool Units Only
When shipped, remote air-cooled units contain a refrigerant holding charge.
The holding charge must be
reclaimed before removing the caps on the remote-condenser tube stubs. Failure to reclaim the
holding charge can lead to property damage and/or personal injury.
Locate the refrigerant liquid-line solenoid valves (usually two per
circuit). Some units may be equipped with manual-lift valves.
Where this is the case:
1. Using two wrenches, remove the manual-stem covers.
2. Turn the manual stems clockwise to open the valves.
stem cover
manual stem
INST
ALLA
TION
EXAMPLE
Appearance, location, and
quantity of component
s
may vary
.
EXAMPLE
Appearance, location, and
quantity of component
s
may vary
.
Manifold (by others) will also be
required for evacuation.
Reclaim
Machine