IMPORTANT:
Cut tubes as necessary using a tube-
cutter only. DO NOT use a saw.
Never apply heat to a refrigerant line
until all pressure has been released -
unsafe pressures could result, causing
violent explosion and serious personal
injury or death. Be sure the area is
well ventilated.
Air-cooled systems must be installed
by qualified refrigeration technicians,
using industry-standard practices.
Dectron, Inc. assumes no
responsibility for improper installa-
tions or for the results of failure to
follow instructions in this manual.
IMPORTANT:
The total length of tube one way
must not be greater than 100 ft.
(30 m). The total equivalent length
must not be greater than 150 ft.
(45 m). The remote condenser
must not be located below the
Ecosaire® unit.
IMPORTANT:
Never allow dirt or other foreign
materials to enter the remote con-
denser or the tubes connecting it
to the Ecosaire® unit. Foreign
material may damage valves and
other components.
If the inside of the tubes is con-
taminated with dirt, oil, sludge,
rust, or other materials, then they
must be thoroughly cleaned.
IMPORTANT:
Never allow liquid water to enter
the remote condenser or the tubes
connecting it. Water must be
removed from the remote con-
denser and the tubes that connect
it to the
Ecosaire®
. Evacuation
will take much longer if liquid water
is present.
Installation Piping Refrigerant Tube
Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only
Total length of tube not to exceed 100 ft one
way.
Horizontal runs of the hot-gas tube should
slope downward 1/4” per 10 ft in the direction
of flow.
The total vertical rise
must not exceed 30 feet.
P-traps must be installed
in the hot-gas riser tubes to
break up the lift into seg-
ments of not more than 15ft.
Tube sizes appear on pre-
vious page.
The total length of tube
must not exceed 100 feet
one way.
The total equivalent
length of tube must not
exceed 150 feet one way.
inverted P-trap
Install access valves
(by others).
P-trap
15 ft
or
less
15 ft
or
less
Use clean and dry type ACR tube only.
Remote Condenser
Remote Condenser
Remote Condenser
Ecosaire
Ecosaire
Ecosaire
Install an access valve in the liquid
tube near the Ecosaire unit.
Install an access valve
in the liquid tube near
the Ecosaire unit.
INST
ALLA
TION
Consult Dectron
before installing a
remote condenser
below an
Ecosaire unit.
Install access valves
(by others).
EXAMPLES
Appearance, location, and
quantity of component
s
may vary
.
Summary of Contents for EN Series
Page 1: ......
Page 103: ...OEM User manual ...
Page 104: ......
Page 106: ......
Page 108: ......
Page 110: ......
Page 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Page 141: ......