The refrigerant expansion valves must be adjusted at startup.
Firmly attach a thermocouple or other temperature sensor to the suction
tubes.
Insulate the sensor and all around the suction tube with 1/2” thick
insulation for at least three inches on either side of the temperature sensor.
Tape the insulation to prevent air flow from changing the temperature
reading.
Locate and identify the refrigerant sight glasses.
Locate and identify the expansion valves associated with each sight glass.
Startup Prepare to Adjust Expansion Valves
Air-Cooled Direct Expansion, Water-Cooled Direct Expansion, Glycol-Cooled
Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool,
& FreeCool Units Only
ST
ARTUP
EXAMPLE
Appearance, location, and
quantity of component
s
may vary
.