Owners Manual Ecosaire
®
EN Series Precision Air Conditioner
Calculate Refrigerant Charge Piping
Installation
Ecosaire
®
July 2009 29
Data subject to change without notice.
Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only
For options, see
Product Description - Model Designation Chart
.
Note: Water- and Glycol-cooled units are shipped with a full refrigerant charge.
The necessary refrigerant charge is made up of three parts - that required to fill the unit, that required to fill the
liquid line, and that required to fill the remote condenser.
Ecosaire Unit
(R-410a lb. per circuit)
Model
EN-027
3.7 =______
EN-035
4.8
=______
EN-042
4.8
=______
EN-051
4.8
=______
EN-068
7.4
=______
EN-079
7.4
=______
EN-087
7.4
=______
EN-102
9.9
=______
Liquid Line
(R-410a lb. per circuit)
O.D. lb./
length
(in.) (ft.) (ft.)
5/8
0.126 X _____ = ______lbs.
3/4
0.185 X _____ = ______lbs.
7/8
0.259 X _____ = ______lbs.
1 1/8 0.441 X _____ = ______lbs.
Condenser
(lb.)
KMG041
21
= _____
KMG051
31
= _____
KMG061
33
= _____
KMG075
48
= _____
KMG085
66
= _____
KVG085
38
= _____
KVG096
38
= _____
KVG106
57
= _____
KVG116
57
= _____
KVG126
76
= _____
KVG160
85
= _____
KVG181
112 = _____
KVG208
112 = _____
KVG239
150 = _____
KVG253
150 = _____
KVG321
170 = _____
____
+ ____
+ ____
_________
Total _____
Add this much R-410a (by others).
Copy this amount into BOX A on the following page.
Example:
An EN-027A has a KMG041 remote condenser. They are connected with 60 feet of 5/8” O.D.
liquid line. The required amount of R-410a is
7.4 lb + (0.126 lb/ft X 60 ft) + 21 lb = 36 lb.