E93.1801EN171 HWB installation manual
69
Programmable in- and outputs
It’s possible to re-program some in- and outputs to other functions. To do this use below list and go to:
Menu\settings\water heater settings\"1122" (installer password) \water heater parameters
water heater pa-
rameter
name
default setting
description
terminal
(117)
Prog. Input 2.
2
DHW flow switch
LV 16-17
(118)
Prog. Input 3.
2
Gas pressure switch
LV 24-25
(122)
Prog. Input 7.
3
Cascade sensor
LV 3-4
(124)
Prog. Input RT.
1
room thermostat on
LV 12-13
(125)
Prog. Output 1.
4
System pump
HV 4-5
(126)
Prog. Output 2.
9
Ext. Igniter
separate connector
(127)
Prog. Output 3.
6
Alarm semiconductor output
HV 10-11
(128)
Prog. Output 4.
18
3-way Valve DHW
HV 3-2-1
To all outputs following applies: maximum current 2 Amp each output.
Total output of all currents combined maximum 3.5 Amp.
The inrush current of the 3-way valve and/or pumps is maximum 8 Amp.
para-
meter
Display:
INPUTS:
re-
mark
para-
meter
Display:
OUTPUTS
:
re-mark
(117)
Prog. Input 2.
0 Disabled
(127)
Prog. Output 3. 0 Disabled
1 DHW flow sensor
N.A.
1 Module pump
N.A.
2 DHW flow switch
2 CH pump
N.A.
3 CH flow sensor
N.A.
3 DHW pump
N.A.
4 CH flow switch
4 System pump
N.A.
(118)
Prog. Input 3.
0 Disabled
5 Cascade pump
N.A.
1 Drain switch
6 Alarm relay
2)
2 Gas pressure switch
7 Filling valve
2)
(122)
Prog. Input 7.
0 Disabled
8 LPG tank
2)
1 T_Flue_2 sensor
N.A.
9 Ext. Igniter
2)
2 T_Flue_2 with blocked flue
N.A.
10 Air damper
2)
3 Cascade sensor
(128)
Prog. Output 4. 0 Disabled
4 Blocked Flue switch
N.A.
1 Module pump
5 CH Sensor
2 CH pump
(124)
Prog. Input RT. 0 room thermostat off
3 DHW pump
1 room thermostat on
4 System pump
Display:
OUTPUTS
:
5 Cascade pump
(125)
Prog. Output 1. 0 Disabled
6 Alarm relay
1 Module pump
7 Filling valve
2 CH pump
8 LPG tank
3 DHW pump
9 Ext. Igniter
4 System pump
10 Air damper
5 Cascade pump
11 empty
6 Alarm relay
12 empty
7 Filling valve
13 empty
8 LPG tank
14 empty
9 Ext. Igniter
15 empty
10 Air damper
16 empty
(126)
Prog. Output 2. 0 Disabled
17 3-way Valve CH
1 Module pump
1)
18 3-way Valve DHW
2 CH pump
1)
19 3-way Valve CH
(power when idle)
3 DHW pump
1)
20 3-way Valve DHW
(power when idle)
4 System pump
1)
5 Cascade pump
1)
6 Alarm relay
1)
7 Filling valve
1)
8 LPG tank
1)
9 Ext. Igniter
1)
10 Air damper
1)
NOTICE
Remarks:
1) Prog. output 2: (ext. igniter); this is a separate connector,
the pin in the middle is for ionization, it has no PE connec-
tion. If earth is needed, it must be connected to the main
earth terminal.
2) Prog. output 3: (alarm relay); this is a triac output with an ac-
tive voltage of 120 VAC, it can only handle resistive loads
between 5 and 50 Watt.
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......