E93.1801EN171 HWB installation manual
38
NOTICE
10.1.2
V
ENT AND AIR INLET RESISTANCE TABLE
Minimum and maximum allowable combined vent and air inlet length
:
- Minimum venting length: two feet (2 ft) for all water heaters
- Maximum venting length: see table below.
Maximum Exhaust Length / Maximum Combustion Air Intake Length
HWB-299
HWB-399
HWB-499
4"
228' / 228'
121' / 121'
92' / 92'
5"
359' / 359'
6"
605' / 605'
For long lengths, check venting pipe and fittings for maximum allowable pressure.
This table may only be used for a single vent/air system for one water heater.
Do
NOT
use this table for common vent systems with cascaded water heaters.
Pipe, elbows, tees - equivalent feet:
for DuraVent PolyPro
Item\ size
4"
5"
6"
1 ft Vent Pipe
1 ft
1 ft
1 ft
1 ft Flex Pipe (same diameter as rigid)
2 ft
2 ft
NA
1 ft Flex Pipe (upsized one diameter)
0.6 ft
NA
NA
45 Elbow
5 ft
6 ft
6 ft
90 Elbow
12 ft
14 ft 14 ft
Tee
19 ft
21 ft 22 ft
Terminals equivalent feet:
for DuraVent PolyPro
WATER
HEATER
TERMINAL
size
part #
HWB-299
HWB-399
concentric roof:
4" vent
4PPS-VKL
4PPS-VK-TCL
37 ft
concentric wall:
4" vent
4PPS-HKL
13 ft
HWB-499
2 pipe wall:
6" vent
6PPS-HSTL
28 ft
Vent and air intake pipe material
Items
Materials
1)
Venting System Standards
Warning
United States
Canada
3)
Flue piping and
Fittings
CPVC Schedule 40
ANSI/ASTM F441
All venting mate-
rial in Canada
must be
ULC S636 ap-
proved.
All Vent and Air-Inlet
materials installed on
gas
fired appliances in
CAN/US must meet the
Standards listed in this
Table.
Failure to comply could
result in fire, serious in-
jury or death.
PVC Schedule 40
ANSI/ASTM D1785
Stainless Steel SS
UL-1738
Polypropylene PP
-
Air inlet piping
and Fittings
2)
PVC - DWV
ANSI/ASTM D2265
Stainless Steel SS
UL-1738
Polypropylene PP
-
Pipe cement
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Primers
PVC/CPVC
ANSI/ASTM F656
Notes:
1 PVC venting (exhaust and air-inlet) is not permitted within the Closet/alcove of a Closet/alcove installation.
2
The air-inlet does not require high temperature pipe material. Check applicable local codes for acceptable materials.
3 Use only vent gas material suitable for flue gas temperatures of 158
⁰
F (70
⁰
C) or higher.
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......