E93.1801EN171 HWB installation manual
43
10.4.1
F
LEXIBLE POLYPROPYLENE
For use of flex pipe, it is recommended to have the vent material in 32°F or higher ambient space before bending
at installation. No bends should be made to greater than 45° and ONLY installed in vertical or near vertical instal-
lations.
Insulation is prohibited from use on all types of plastic venting material: PVC, CPVC, and Poly-
propylene.
Use only the adapters and vent system listed.
DO NOT mix vent systems of different types or manufacturers.
Failure to comply could result in severe personal injury, death, or substantial property damage.
All vent connections MUST be secured by the vent manufacturer's joint connector.
The installer must use a specific vent starter adapter at the flue collar connection. The adapter
is supplied by the vent manufacturer to adapt to its vent system.
Installations must comply with applicable national, state, and local codes.
For Canadian installation, polypropylene vent must be listed as a ULC-S636 approved system.
Installation of a polypropylene vent system should adhere to the vent manufacturer’s installation
instructions supplied with the vent system.
10.4.2
S
TAINLESS STEEL VENT
.
This product has been approved for use with stainless steel using the manufacturers listed.
Approved stainless steel vent pipe and fittings.
SUPPLIER
TYPE
Duravent
FasNSeal, FasNSeal Flex
Security Chimneys
Secure Seal SS/SSD/SSID
Heat Fab
Saf-T EZ Seal
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking pre-
caution to ensure no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially de-
signed adapters and sealing method, see manufacturer’s instructions.
Use only the materials, vent systems, and terminations listed.
DO NOT mix vent systems of different types or manufacturers. Failure to comply could result
in severe personal injury, death, or substantial property damage.
The installer must use a specific vent starter adapter at the flue collar connection, supplied
by the vent manufacturer to adapt to its vent system.
Installations must comply with applicable national, state, and local codes. Stainless steel
vent systems must be listed as a UL-1738 approved system for the United States and a
ULC-S636 approved system for Canada.
Installation of a stainless-steel vent system should adhere to the stainless-steel vent manu-
facturer’s installation instructions supplied with the vent system.
Approved Stainless Steel Terminations.
Duravent
Security Chimneys
HeatFab
FasNSeal
Secure Seal
Saf-T EZ Seal/ EZ 316
WATER
HEATER
TERMINATION
TERMINATION
TERMINATION
HWB-299
HWB-399
FSBS4 (bird screen
wall)
FSRC4 (rain cap roof)
SS4STAU (screen termination
SS4RC (rain cap roof)
5490CI (horizontal termination)
5400CI (rain cap)
HWB-499
FSBS6 (bird screen
wall)
FSRC6 (rain cap roof)
SS6STAU (screen termination
SS6RC (rain cap roof)
5690CI (horizontal termination)
5600CI (rain cap)
DANGER
NOTICE
NOTICE
WARNING
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......