E93.1801EN171 HWB installation manual
59
Do not operate the appliance with the rain cap removed
on the concentric terminations or
recirculation of combustion products may occur.
Water may also collect inside the larger combustion air pipe and flow to the burner enclosure.
Failure to follow this warning could result in product damage or improper operation, personal
injury, or death.
Do not allow insulation or other materials to accumulate inside the pipe assembly when in-
stalling through the hole.
Ensure termination height is above the roof surface or anticipated snow level (12 inches (305
mm) in U.S.A. or 18 inches (457 mm) in Canada) as shown in figure above.
DO NOT use field-supplied couplings to extend
concentric terminations
. Airflow restriction will
occur.
Multi venting vertical terminations
When two (2) or more direct vent appliances are vented near each other, each appliance must be individually
vented (see figure below). NEVER common vent or breach vent this appliance. When two (2) or more direct vent
appliances are vented near each other, two (2) vent terminations may be installed as shown in figure below. It is
important that vent terminations be installed as shown to avoid recirculation of flue gases.
Concentric vent and combustion air vertical termination multiple water heaters.
WARNING
NOTICE
CAUTION
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......