E93.1801EN171 HWB installation manual
88
Lockout codes
Lock-
out
code
Error
Description
Cause
Solving
0
E2PROM_READ
_ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
1
IGNIT_ERROR
Five unsuccessful igni-
tion attempts in a row
no gas, wrongly ad-
justed gas valve
check gas supply and ad-
just gas valve, reset BCU
2
GV_RELAY_
ERROR
Failure detected in the
gas valve relay
short circuit in coil of
the gas valve, water
on wiring or gas valve
reset BCU replace gas valve
or wiring harness
3
SAFETY_RE-
LAY_ERROR
Failure detected in
safety relay
safety relay is not
working correctly
reset BCU or replace BCU
4
BLOCKING_
TOO_LONG
Control had a blocking
error for more than 20
hours
blocking code active
for more than 20 hours
reset and check blocking
code
5
FAN_ERROR_
NOT_RUNNING
Fan is not running for
more than 60 seconds
electrical wiring not
correctly connected, or
Fan is malfunctioning
Check wiring or replace Fan
if not solved check fuse on
BCU or replace BCU
6
FAN_ERROR_
TOO_SLOW
Fan runs too slow for
more than 60 seconds
electrical wiring not
correctly connected, or
Fan is malfunctioning
Check wiring or replace Fan
if not solved check fuse on
BCU or replace BCU
7
FAN_ERROR_
TOO_FAST
Fan runs too fast for
more than 60 seconds
electrical wiring not
correctly connected, or
Fan is malfunctioning
Check wiring or replace Fan
if not solved check fuse on
BCU or replace BCU
8
RAM_ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
9
WRONG_EEPR
OM_SIGNA-
TURE
Contents of E2prom is
not up to date
outdated E2prom
reset BCU or replace BCU
10
E2PROM_
ERROR
Wrong safety parame-
ters in E2prom
wrongly programmed
BCU or PB
reset BCU or replace BCU
11
STATE_ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
12
ROM_ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
13
APS_NOT_
OPEN
Air pressure switch not
opening during pre-
purge 0
electrical circuit is
short circuited, or APS
is jammed
check wiring or replace APS
14
APS_NOT_CLO
SED_IN_PRE_
PURGE
Air pressure switch not
closing during pre-
purge 1
no air transport to the
burner; flue or air inlet
is blocked, or APS is
jammed or air signal
hose not connected to
the air intake pipe or
water in hose
Check if there are any ob-
structions in the flue or air in-
take, replace APS if jammed,
connect air hose to the air in-
take pipe, remove any water
from the hose.
15
MAX_TEMP_
ERROR
The external overheat
protection is enabled
or the T_Supply sen-
sor measures a temp.
of over Prot_Over-
heat_Temp - SGOver-
heat_Duplex_Toler-
ance for a period of
Max_Value_Period
Burner door clixon
tripped because of
overheating of the
burner door or the wa-
ter flow is restricted, or
back wall thermal fuse
has tripped because
rear wall insulation
disc (combustion
chamber)
is damaged
or
broken.
Check burner door gasket
and replace burner door gas-
ket and reset clixon on
burner door or check pump
and waterflow and replace
pump or increase water flow
check also if valves are
closed or check if rear wall
fuse is broken if so replace
and also replace rear wall in-
sulation disc (combustion
chamber).
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......