E93.1801EN171 HWB installation manual
84
cont:
4.2.1 Boiler parameters
min.
max.
Default
unit
Access
level
Description:
Dis-
play
no:
DHW Tank Hyst. Up
0
(0)
18
(10)
7.2
(4)
°F
(°C)
Installer
Set the DHW tank hysteresis
up
37
DHW Tank Supply Extra
0
(0)
54
(30)
0
(0)
°F
(°C)
Installer
Set the DHW tank supply
setpoint offset
38
DHW Priority
0
2
on
0-2
Installer
Set the DHW priority mode
42
DHW Max. Priority Time
1
255
60
min.
Installer
Set the maximum DHW pri-
ority time
43
DHW Pump Overrun
0
900
20
sec.
Installer
Set the DHW post-circulation
time
44
DHW/Tank Setpoint
102
(39)
158
(70)
140
(60)
°F
(°C)
Installer
Set the DHW setpoint
48
DHW Store Setpoint
32
(0)
50
(10)
140
(60)
°F
(°C)
Installer
Set the DHW storage set-
point
115
PreHeat mode
on
off
off
Installer
Set the PreHeat Eco mode
64
Prog. Input 2.
0
4
2
#
Installer
Select the function for pro-
grammable input 2
117
Prog. Input 3.
0
2
2
#
Installer
Select the function for pro-
grammable input 3
118
Prog. Input 7.
0
5
3
#
Installer
Select the function for pro-
grammable input 7
122
Prog. Input RT.
0
1
1
#
Installer
Select the function for the
programmable RT input
124
Prog. Output 1.
0
10
4
#
Installer
Select the function for pro-
grammable output 1
125
Prog. Output 2.
0
10
9
#
Installer
Select the function for pro-
grammable output 2
126
Prog. Output 3.
0
10
6
#
Installer
Select the function for pro-
grammable output 3
127
Prog. Output 4.
0
20
18
#
Installer
Select the function for pro-
grammable output 4
128
Mod. Pump dT
9
(5)
72
(40)
27
(15)
°F
(°C)
Installer
Set the modulating pump tar-
get delta temperature
133
Mod. Pump Start Time
0
255
60
sec.
Installer
Set the modulating pump
start up time
134
Mod. Pump Type
wilo
Installer
Set the modulating pump
model
135
Mod. Pump Mode
20
100
On/off
o/f or
mod.
Installer
Set the modulating pump
mode
136
Mod. Pump Min Pwr
45
%
Installer
Set the modulating pump
minimum duty cycle
137
Appliance Type
50
55
50
#
Installer
Set the appliance type
138
Dair active
0
1
yes
Yes/
No
Installer
Enable/disable the De-Air
function
139
Anti Legionella Day
mon
sun
Sunday
Installer
Select the day for the anti-le-
gionella cycle
107
Anti Legionella Hour
0
23
0
hrs.
Installer
Select the time for the anti-
legionella cycle
108
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......