Configuration of the digital inputs
Ju
mp
er
Voltag
e
Function / conditions
Diagram
230 V
AC
(factor
y
setting
)
Only AC voltage signals are supported.
The N conductor
must
be connected on the terminal level (50..72), here using the
example of terminals 50..62 with jumper.
-
PE
For mixed operation of the voltage levels!
Low voltage (230 V AC) and safety extra-
low voltage (24 V AC/DC)
must
be separated by a digital input connected to PE, here
using the example of terminals 64/65.
-
24 V
AC/DC
AC and DC low voltage signals are detected and evaluated.
Exception:
acquisition of 24 V
DC
counter pulses (S0 interface)
To count S0 pulses, these must be at least 95 ms apart, otherwise faster pulse
sequences will not be detected. The pulse width must be at least 30 ms.
GND of 24 V
DC
must
be connected on the terminal level (50..72), here using the
example of terminals 66..72 with jumper.
For details about the assignment, see chapter
Assignment of the digital inputs - 230 V AC / 24 V AC/DC
.
10.2.3 Assignment of the relay outputs - 230 V AC / 24 V AC/DC
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
BEFORE
connecting and disconnecting, it must be checked that
no voltage is present
at the
230 V AC relay outputs!
Overvoltage category II / contamination degree 2:
All connections of the device provided for
operation with 230 V AC supply voltage
must
be wired with the same outer conductor (L). 400 V AC
between neighbouring connection terminals is
not
permitted!
No mixed operation of the voltage levels!
Low voltage (230 V AC)
and
safety extra-low voltage
(24 V AC/DC) must
not
be connected together
at the relay outputs!
•
•
ATTENTION
Fuse protection for the supply line of the relay outputs:
A circuit breaker with the following
characteristics
must
be used per relay output:
Rated current for 230 V AC: 6(3) A
Tripping characteristic (type): B
Damage to the connector socket:
Note the
handling of wide COMBICON plugs
.
Manual control switch on the base and extension module:
The relay outputs 1..8 (not 9 and 10) of
the base module and all relay outputs of the extension module can be manually overridden via the
associated manual control switches on the front, for details see chapter
Practical tip:
The configured functionality of the relay outputs should be noted on the front in the
spaces provided to make it later manual operation easier.