10.2.2 Assignment of the digital inputs - 230 V AC / 24 V AC/DC
Digital inputs on the base module
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
BEFORE
connecting and disconnecting, it must be ensured that
no voltage
is present at all
connections of the controller.
Overvoltage category II / contamination degree 2:
All connections of the device provided for
operation with 230 V AC supply voltage
must
be wired with the same outer conductor (L). 400 V AC
between neighbouring connection terminals is
not
permitted!
Mixed operation of the voltage levels!
If digital inputs with low voltage (230 V AC)
and
safety extra-
low voltage (24 V AC/DC) are required on
one
SIOX module, these
must
be separated by a
digital
input
connected to
PE!
Practical tip:
Use of 2 separate SIOX modules to handle only one voltage level per module.
ATTENTION
Configuration of the digital inputs:
For the digital inputs, ensure that the jumper position is correctly
configured for 230 V AC or 24 V AC/DC. If 230 V AC is applied to a digital input that has been
configured for 24 V AC, this results in destruction of the digital inputs! For details, see chapter
Configuration of the digital inputs 230 V AC and 24 V AC/DC
Damage to the connector socket:
Observe the
Handhabung breiter COMBICON-Stecker
!