Firmware: V2.18 / V--
26.10.2022
58/119
7.4 Changes of GLT 5010 compared to GLT 3010
The data point description is embedded in the CODESYS program of the GLT 5010. The controller, together
with the system centre, then takes care of the distribution in the system.
With the Signal List Tool (per controller), CODESYS export files with the name "EA_DDC_
n
_config.exp" are
created.
The respective file is imported as usual.
Under "Resources → Global Variables → Signal List → GLTCFG" you will then find the two structure fields
gltcfg1 and gltcfg2.
As a last step, the pointers to the structure fields must be made known
once
to the operating system of the
controller via the function Set_GLTCFG(). In the example application, the module INIT_T is suitable for this
purpose:
When starting the controller, or more precisely: the CODESYS application, the operating system then
automatically transfers the complete configuration file "GLT.CFG" to the system centre CI 5x00 or Virtus.