Firmware: V2.18 / V--
26.10.2022
109/119
1.
2.
3.
4.
Connection of the Modbus modules to the base module and the power supply
Modbus modules can be connected via the
on the base module to expand the I/Os.
Configuration of the Modbus modules
Setting of the Modbus address
Disconnect module from the power supply.
Set Modbus address "
1..99
" (address selector switches X10 and X1).
Example:
X10 = 4 = 4 x 10 = 40 and
X1 = 9 = 9 x 1 = 9
Modbus address = X10 + X1 = 40 + 9 = 49
Connect 100 Ohm terminating resistor to the last Modbus module (drawing on the left).
Supply power to module.
The communication parameters of the Modbus interface are configured in CODESYS.
* Note:
A terminating resistor of 100 Ohm
must
be installed at the end of the Modbus cable
(drawing on the left, part number W100R00004), for details see
.
The Modbus modules are set with
parity = even
and
bit rate of 19200 bit/s
at the factory. Further details
can be found in the description of the Modbus modules.