77
InStALLAtIon And opErAtIon mAnuAL
25-13741-E
January 2020 www.eaton.com
14. Logging facility
14.2 Fault logs
All Faults occurring on the system – MX and connected OS are logged on the panel.
The fault log is accessible using the display under “Fault Log” option. Date and time
stamp is recorded for all faults. According to specifications by BS 5839:2011, all fault
indications are indicated within 100s of their occurrence. If any fault occurs while a
call is in progress, audible indication for fault is suppressed. It will be restored within
100s of ending of call.
Fault Type
Fault Name
Description
Power Supply
PSU Not Found
Panel is not able to communicate with PSU
AC PSU Fail
AC power source is not available
DC PSU Fail
DC power source is not available
Battery Charger
Battery is not getting charged properly / battery is
not connected
Battery Fault
Incorrect or broken battery is connected.
Battery Resistance
Battery resistance has increased over time beyond limit and
needs replacement.
In case of above faults, check the power connections – AC mains to pSu, pSu to
main board, pSu to battery, replacement of batteries. If the faults persist, call for
engineering support.
Network Faults –
CAN / Outstation loop
CAN A/B Error
Fault on OS wiring - data lines between Panel and OS
CAN A/B Loop Break
Fault on OS loop - data lines between Panel and OS,
data lines between OS-OS
PSU A/B Short Circuit
Fault on OS loop – Power lines are shorted
OS Missing
Outstation previously configured is not responding
OS Unknown
An unknown OS is added in the loop
OS Position
Position/Address of OS is changed in the loop
OS Invalid
Device connected is not recognized by the panel
In case of above faults, check the loop wiring connections for any break or loose
connection. perform outstation learn procedure to confirm the changes in oS
position or addition.
Fault Log (1-15)
01/02/19 12:30.02
Panel In Fault
1
02/03/19 10:54.30
Mic. Open Circuit
2
06/03/19 09:05.50
Speaker Open Circuit
3