POWER WIRING INSTALLATION NOTES
013106
B
164201590---4
12 of 13
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-30
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
13.
External IAC rectifier and bypass input overcurrent protection is not provided by this
product, but is required by codes. Refer to Table D through Table F for wiring
requirements.
14.
Table R lists the maximum rating for rectifier input circuit breakers and Table S lists the
maximum rating for bypass input circuit breakers.
Table R. Maximum IAC Rectifier Input Circuit Breaker
Ratings
IAC Model
Input Voltage Rating
208V
100 kVA
80% Rated
450A
100% Rated
350A
120 kVA
80% Rated
500A
100% Rated
450A
160 kVA
80% Rated
700A
100% Rated
600A
Table S. Maximum IAC Bypass Input Circuit Breaker Ratings
IAC Model
Input Voltage Rating
208V
480V
40 kVA
80% Rated
175A
70A
100% Rated
150A
60A
50 kVA
80% Rated
225A
100A
100% Rated
175A
80A
60 kVA
80% Rated
250A
125A
100% Rated
200A
90A
80 kVA
80% Rated
350A
150A
100% Rated
300A
125A
100 kVA
80% Rated
450A
200A
100% Rated
350A
150A
120 kVA
80% Rated
500A
225A
100% Rated
450A
175A
160 kVA
80% Rated
700A
300A
100% Rated
600A
250A
C A U T I O N
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table R in accordance with the NEC, ANSI/NFPA 70.