POWER WIRING INSTALLATION NOTES
013106
B
164201590---4
8 of 13
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-26
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
Table K. IAC Maintenance Bypass Power Cable Terminations
(120/100 and 120/120 kVA 208V/208V)
Terminal Function
Terminal
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input to MIS from UPS
MIS–1
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
MIS–3
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
MIS–5
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Input to Maintenance
Bypass
E6
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E7
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E8
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Input to Optional RIB
E1
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E2
Phase B 2 --- #2---500 kcmil
42.4 (375))
3/8
″
Hex
E3
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Output from Optional
RIB to UPS
RIB–2
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
RIB–4
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
RIB–6
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Output from Optional
BIB to UPS
BIB–2
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
BIB–4
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
BIB–6
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Output to
Critical Load
E9
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E10
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E11
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
Neutral
E12
Neutral
12 --- #2---600 kcmil
56.5 (500)
1/2
″
Hex
Ground
Gnd
Ground
6 --- #14---1/0
5.6 (50)
Slotted
Table L. IAC 1+1 Parallel Redundant Power Cable Terminations
(160/100, 160/120, and 160/160 kVA 208V/208V)
Terminal Function
Terminal
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input to MOB 1 from
UPS
MOB1–2
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
MOB1–4
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
MOB1–6
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Input to MOB 2 from
UPS
MOB2–2
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
MOB2–4
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
MOB2–6
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Output to
Critical Load
(without SLB)
E9
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E10
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E11
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
AC Output to
Critical Load
(with SLB)
E9
Phase A 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E10
Phase B 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
E11
Phase C 2 --- #2---500 kcmil
42.4 (375)
3/8
″
Hex
Neutral
E12
Neutral
16 --- #2---600 kcmil
56.5 (500)
1/2
″
Hex
Ground
Gnd
Ground
6 --- #14---1/0
5.6 (50)
Slotted