PHYSICAL FEATURES AND REQUIREMENTS
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
013106
B
Installation Information
A-6
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
1.
The IAC equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Drawing 164201590---8.
2.
The IAC is palleted separately for shipping.
3.
Do not tilt cabinets more than
10
˚
during handling.
4.
Dimensions are in millimeters (inches).
Table A. Equipment Weight
Component/Model
Weight
kg (lb)
Shipping
Installed
Point Loading
Powerware 9390 IAC with an MBP and MIS
333.4 (735)
303.9 (670)
4 at 76 (167.5)
NOTES:
1. For IAC with a BIB add 6.8 kg (15 lb).
2. For IAC with a BIB and RIB add 18.1 kg (40 lb).
Powerware 9390 IAC with MOB1 and MOB2
333.4 (735)
303.9 (670)
4 at 76 (167.5)
NOTES:
1. For IAC with an SLB add 6.8 kg (15 lb).
2. For IAC with an MBP and MIS add 13.6 kg (30 lb).
5.
The clearances required around the IAC are shown in Table B.
Table B. IAC Clearances
From Top of Cabinet
Minimum clearance over the cabinet is
457.2 mm (18 inches) for ventilation
From Front of Cabinet
914.4 mm (36 inches) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required